Advertisement

communication channel of the FX (RS-422 8-pin Mini-DIN or RS-232C 9-pin
D-sub). The cable names and details for each case are illustrated below:
Connection to an RS-422 FX communication channel
Cable Name
GT01-C10R4-8P
GT01-C30R4-8P
GT01-C100R4-8P
GT01-C200R4-8P
GT01-C300R4-8P
Connection to an RS-232C FX communication channel
Cable Name
GT01-C30R2-9S
* - Special Adapters require an additional FX**-CNV-BD or, for the FX3U only, a
Communication Expansion Board.
Programming Cables:
The GT11 Series GOTs come pre-installed with an OS only without
any project data. To download a project from a PC running GT Designer2 to
the GOT, a programming cable is required to connect the PC to one of the
communication interfaces. For a new out-of-the-box GOT, the easiest way to
connect to the GOT is through the USB Mini-B type port on the front panel
with a standard USB cable. After setting up the GOT communication settings
from the GOT main menu or with GT Designer2, the RS-422 and RS-232C
interfaces can also be used for program transfer. Connection via USB is
shown below.
Note: This document is for reference only. For detailed settings and safety information refer to the respective product manual.
Length
FX Comm. Equipment
1m
Programming Port
3m
FX3U-422-BD
10m
FX2N-422-BD
20m
FX1N-422-BD
30m
Length
3m
FX Comm. Equipment
FX3U-232-BD
FX3U-232ADP(-MB)*
FX2N-232-BD
FX2NC-232ADP*
FX1N-422-BD