Mitsubishi Electric LOSSNAY PZ-25RF8-E Handbook page 20

Table of Contents

Advertisement

LGH-150RX
-E, LGH-200RX
5
A
B
M
M
2
2
SUPPLY
SUPPLY
FAN MOTOR
FAN MOTOR
A: The motor produced
from February 2014
B: The motor produced
until January 2014
M
1
EXHAUST
FAN MOTOR
A
B
M
M
2
2
SUPPLY
SUPPLY
FAN MOTOR
FAN MOTOR
M
1
EXHAUST
FAN MOTOR
CN16
(Unchanged a-contact)
HI
LO
BY-PASS
NOTE 1.TM1, TM2, TM3, TM4, TB5 shown
in dotted lines are field work.
2.Isolator should be provided by the customer.
3.Be sure to connect the grounding wire.
*Attention
With this product, the wiring installation method will
vary according to the design of the system.
Perform electrical installation to meet local electrical regulations.
. Always use double insulated PVC cable for the transmission cables.
. Wiring work must be performed by qualified professionals.
. All supply circuits must be disconnected before obtaining access to the terminal devices.
M1:
Motor for exhaust fan
M2:
Motor for supply fan
C:
Capacitor
GM:
Motor for By-pass operation
LS:
Microswitch
TH1:
Thermistor for outside air
TH2:
Thermistor for return air
SW1:
Switch (Main/Sub change)
SW2, 5:
Switch (Function selection)
TM1:
Terminal block (Power supply)
TM2:
Terminal block(External control input)
TM3:
Terminal block (Monitor output)
TM4:
Terminal block
(Transmission cable and monitor output)
TB5:
Terminal block (M-NET Transmission cable)
TAB1,TAB2: Connector (Power supply)
TR1:
Control circuit transformer
TR2,TR3:
By-pass operation transformer
-E
5
BROWN
x103
BLACK
GREY
x103
YELLOW
x102
x102
C
x101
x101
RED
ORANGE
BLUE
x203
x203
WHITE
x202
C
x202
x201
x201
BROWN
BLACK
GREY
CN32
YELLOW
TH1 (OA)
C
ORANGE
ORANGE
ORANGE
ORANGE
RED
TH2 (RA)
ORANGE
BLUE
X12
X11
WHITE
C
TM3
6
7
8
By-pass or Delay2
monitor output 6 , 7
Malfunction monitor
BROWN
output 7 , 8
RED
MAX 240VAC 1A
External control input
ORANGE
24VDC 1A
1
YELLOW
MIN 220VAC 100mA
GREEN
5VDC
100mA
Unchanged a-contact
Definition of Symbols
BROWN
RED
TAB3
TAB5
BLACK
TAB1
GREY
CN10
YELLOW
TAB2
CN1
ORANGE
BLUE
CN9
WHITE
CN7
CN2
CN16
SW2
SW1
CN5
SW5
TM4
10
SA1 SA2
X10
9
2
1
TM2
TB5
1
2
3
A
B
S
Shield Wire
12V or 24V DC
M-NET
transmission
Mr.Slim
cable
(non-polar)
MELANS
*When the optional Remote Controller PZ-60DR-E
3
is used as the M-NET System, connect it to
2
of TM4 terminal block, and connect M-NET
transmission wire to
block.
TM4
2
1
TB5 (M-NET)
A
B
S
M-NET
transmission
Shield Wire
cable
2nd or later main units
*Specifications may be subject to change without notice.
X10,X11,X12: Relay contact
X101,X102,X103: Relay Supply fan speed control
X201,X202,X203: Relay Exhaust fan speed control
CN1:
Connector (Transformer primary)
CN2:
Connector (Transformer secondary)
CN5:
Connector (Thermistor)
CN6:
Connector(Microswitch)
CN7:
Connector (Motor for By-pass operation)
CN9:
Connector (Fan motor)
TAB3:
Tab connector (Fan motor)
TAB5:
Tab connector (Fan motor)
CN9:
Connector (Fan motor)
CN10:
Connector (Fan motor)
CN16:
Connector(High/Low/By-pass switch)
CN32:
Connector (Remote control selection)
SA1:
Address setting rotary switch (10 digit)
SA2:
Address setting rotary switch (1 digit)
SYMBOL
— 20 —
POWER SUPPLY
220-240V 50Hz
Isolator
TM1
L
L
N
N
PE
BLUE
BROWN
TR1
BLUE
RED
BLACK
RED
BLACK
LS
WHITE
TR2
GM MG
BLACK
BROWN
BROWN
LS
GM MG
BLACK
Operation or Delay1
monitor output
MAX 240VAC 2A MIN 220VAC 100mA
24VDC 2A
5VDC
100mA
(*1)
PZ-
60DR-E
2nd remote controller  (Max. two remote controllers installable)
2nd LOSSNAY unit (Up to max 15 units)
Transmission
cable
(non-polar)
1
A
B
,
on TB5 terminal
(*1)
Optional Remote controller
(PZ-60DR-E)
2nd remote controller
(Max. two remote controllers
installable)
(*1)
PZ-41SLB-E and PZ-52SF-E cannot
be used when using PZ-60DR-E.
: Indicates terminal block.
Board insertion connector or fastening
connector of control board.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents