4.4
Correlation between gas pressure and burner output
To obtain the maximum burner output with natural gas (Fig. 3), a
pressure of 9.3 mbar measured at the pipe coupling are needed
(M2, Fig. 10 on page 12) with the combustion chamber at 0 mbar
and gas G20 - Ncv = 10 kWh/Nm
4.5
Burner description
20073319
1
Flange with insulating gasket
2
Air damper adjustment assembly
3
Head holder assembly
4
Pressure test point
5
Combustion head
4.6
Burner equipment
Flange screws and nuts for heat generator fixing . . . . . . . No. 4
Screw and nut for flange. . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Flange with insulating gasket . . . . . . . . . . . . . . . . . . . . . . . No. 1
Gas attachment tube with fixing screws and nuts . . . . . . . No. 1
Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Technical description of the burner
3
3
(8,570 kcal/Nm
).
To obtain the maximum burner output with LPG, a pressure of 11
mbar measured at the pipe coupling are needed with the com-
bustion chamber at 0 mbar (Pci = 23.000 kcal/Nm
Thermal power
6
Air damper
7
Air intake
8
Gas attachment
9
Capacitor
8
GB
20083156
3
)
Fig. 3
Fig. 4
20071805