SAFETY WARNINGS FOR SAFETY REASONS, THE TQ4000 MUST BE INSTALLED, OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND THIS INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING THE TQ4000 THE OPERATION DESCRIBED IN THIS DOCUMENT IS THE INTENDED USE OF THE TQ4000.
TQ Environmental LTD Product Manual TQ 4000 Table of Contents INSTALLATION ....................7 TQ4000 SETUP AND CONFIGURATION ............10 Set Number of Channel ...................... 10 Set Number of Relays ......................10 Configure Channel ......................10 2.3.1 Set Location ......................... 10 2.3.2...
Page 6
Setting the Flammable Gas Sensor Head Voltage ............... 17 Setting the Sensor Zero ...................... 17 CALIBRATION AND SETUP ................19 Zero Adjustment ........................ 19 Span Adjustment ........................ 19 FRONT PANEL WARNING LED’S AND BUTTONS ..........20 Front Panel Warning Lamps....................20 Front Panel Button Functions .....................
1.3. Fit the gas detection control unit to the wall in the appropriate position. The TQ4000 can be fixed in any position to allow cable entry top or bottom. It is recommended that the unit be situated away from heavy electrical loads or equipment that emits high levels of RFI.
2. TQ4000 Setup and Configuration The TQ4000 can be configured via a menu system. The menu system is manipulated using the MENU, UP, DOWN, and SELECT buttons on the TQ4000 main board. The Menu System is password protected and when the MENU button is pressed the user is prompted to enter the system password.
TQ Environmental LTD Product Manual TQ 4000 <SPACE> character and press the SELECT button. When the SELECT button has been pressed the next character on the right will be displayed. To accept the channel location description the user must press the MENU button.
using the UP and DOWN buttons. The standard available sensor units are as follows: PPM, %LEL, %VOL, and MGM. For the user defined sensor units option, the user must use the UP or DOWN buttons to cycle through the alphanumeric characters, pressing the UP and DOWN buttons simultaneously will toggle between uppercase and lowercase characters.
TQ Environmental LTD Product Manual TQ 4000 before the alarm is generated. During the alarm delay the appropriate alarm LED’s will flash intermittently while the gas concentration has exceeded the alarm set point. The default setting is for no alarm delay, that is, 0 seconds.
2.4. Set Relays This option is applicable to the selected channel only. If, for example, the Fault Relay number is required to be applicable for all channels then it would be more convenient to use the Set Common Relays menu option. 2.4.1.
TQ Environmental LTD Product Manual TQ 4000 2.4.7. Set Alarm 2 Relay Pressing the SELECT button will assign the selected relay as the Alarm 2 relay. 2.4.8. Clear Alarm2 Relay Pressing the SELECT button will clear the selected relay as the Alarm 2 relay.
TQ Environmental LTD Product Manual TQ 4000 Initial Setting Up Of Flammable Sensor Cards On flammable sensors there is a requirement to set the zero on the electronic zero on the associated flammable sensor card. This is only required to be done once at installation, after installation any drift can be compensated by the zero procedure in set up.
TQ Environmental LTD Product Manual TQ 4000 Calibration and Setup It is important to ensure that the initial set up of all types of sensor is performed to ensure that they are wired correctly and pre calibration set ups have been observed and are used in the manner described.
To inhibit a channel, that is, disable the relays for a particular channel; the user must press the UP button on the TQ4000 main board when the CHANNEL LED is indicating the desired channel. The INHIBIT LED will illuminate.
To release the hold function the user must keep the HOLD button pressed for a minimum of two seconds. The TQ4000 will then resume normal scanning of channels. 5.2.4. Lamp Test To test the front panel LED’s are operational, the user may press the...
The user must then press the SELECT button on the TQ4000 main board to start the system test. To exit the system test the user must press the UP button on the TQ4000 main board. The TQ4000 will revert to normal system operation.
PCB. Bring voltage up to 2.00V and recalibrate. Check that gas can is not empty and that there is an airtight seal around the gassing cup. For TQ flammable sensors use TQ gassing cup. 7.4. Flammable gas sensor moves erratically when gassed Check the control electronics by evoking test mode and allowing unit to cycle through.
7970V. 8.3. Infra-red and other 3-wire 4-20mA Sensors 3 wire systems indicate that the sensor at the end of the TQ4000 requires power. The TQ4000 can adequately drive up to 3x24Volt sensors each requiring less than 0.25W per sensor.
Product Manual TQ 4000 Modbus Communications The TQ4000 unit features dual channel Modbus communications over 2 serial RS485 lines. This communication allows remote interrogation of the channel concentrations and the status of the channel alarms and fault conditions. It is also possible for remote alarm mute and alarm reset functions to be performed.
Page 26
Modbus Register Addresses For TQ4000 Input Register Starting Starting Number Number Number (0x04) Address(High) Address(Low) Registers(High) Registers(Low) of Bytes Station Number 0x00 0x01 0x00 0x01 Read (0x04) Write (0x10) Channel 1 Conc. 0x00 0x02 0x00 0x01 Channel 2 Conc. 0x00...
Page 30
No part of the hardware or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of TQ Environmental LTD...
Page 31
SAFETY WARNINGS FOR SAFETY REASONS, THE TQ4000 MUST BE INSTALLED, OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND THIS INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING THE TQ4000 THE OPERATION DESCRIBED IN THIS DOCUMENT IS THE INTENDED USE OF THE TQ4000.
Page 32
TQ Environmental LTD Product Manual TQ 4000 Table of Contents INSTALLATION ....................7 TQ4000 SETUP AND CONFIGURATION ............10 Set Number of Channel ...................... 10 Set Number of Relays ......................10 Configure Channel ......................10 2.3.1 Set Location ......................... 10 2.3.2...
Page 33
Setting the Flammable Gas Sensor Head Voltage ............... 17 Setting the Sensor Zero ...................... 17 CALIBRATION AND SETUP ................19 Zero Adjustment ........................ 19 Span Adjustment ........................ 19 FRONT PANEL WARNING LED’S AND BUTTONS ..........20 Front Panel Warning Lamps....................20 Front Panel Button Functions .....................
1.3. Fit the gas detection control unit to the wall in the appropriate position. The TQ4000 can be fixed in any position to allow cable entry top or bottom. It is recommended that the unit be situated away from heavy electrical loads or equipment that emits high levels of RFI.
2. TQ4000 Setup and Configuration The TQ4000 can be configured via a menu system. The menu system is manipulated using the MENU, UP, DOWN, and SELECT buttons on the TQ4000 main board. The Menu System is password protected and when the MENU button is pressed the user is prompted to enter the system password.
TQ Environmental LTD Product Manual TQ 4000 <SPACE> character and press the SELECT button. When the SELECT button has been pressed the next character on the right will be displayed. To accept the channel location description the user must press the MENU button.
using the UP and DOWN buttons. The standard available sensor units are as follows: PPM, %LEL, %VOL, and MGM. For the user defined sensor units option, the user must use the UP or DOWN buttons to cycle through the alphanumeric characters, pressing the UP and DOWN buttons simultaneously will toggle between uppercase and lowercase characters.
TQ Environmental LTD Product Manual TQ 4000 before the alarm is generated. During the alarm delay the appropriate alarm LED’s will flash intermittently while the gas concentration has exceeded the alarm set point. The default setting is for no alarm delay, that is, 0 seconds.
2.4. Set Relays This option is applicable to the selected channel only. If, for example, the Fault Relay number is required to be applicable for all channels then it would be more convenient to use the Set Common Relays menu option. 2.4.1.
TQ Environmental LTD Product Manual TQ 4000 2.4.7. Set Alarm 2 Relay Pressing the SELECT button will assign the selected relay as the Alarm 2 relay. 2.4.8. Clear Alarm2 Relay Pressing the SELECT button will clear the selected relay as the Alarm 2 relay.
TQ Environmental LTD Product Manual TQ 4000 Initial Setting Up Of Flammable Sensor Cards On flammable sensors there is a requirement to set the zero on the electronic zero on the associated flammable sensor card. This is only required to be done once at installation, after installation any drift can be compensated by the zero procedure in set up.
TQ Environmental LTD Product Manual TQ 4000 Calibration and Setup It is important to ensure that the initial set up of all types of sensor is performed to ensure that they are wired correctly and pre calibration set ups have been observed and are used in the manner described.
To inhibit a channel, that is, disable the relays for a particular channel; the user must press the UP button on the TQ4000 main board when the CHANNEL LED is indicating the desired channel. The INHIBIT LED will illuminate.
To release the hold function the user must keep the HOLD button pressed for a minimum of two seconds. The TQ4000 will then resume normal scanning of channels. 5.2.4. Lamp Test To test the front panel LED’s are operational, the user may press the...
The user must then press the SELECT button on the TQ4000 main board to start the system test. To exit the system test the user must press the UP button on the TQ4000 main board. The TQ4000 will revert to normal system operation.
PCB. Bring voltage up to 2.00V and recalibrate. Check that gas can is not empty and that there is an airtight seal around the gassing cup. For TQ flammable sensors use TQ gassing cup. 7.4. Flammable gas sensor moves erratically when gassed Check the control electronics by evoking test mode and allowing unit to cycle through.
7970V. 8.3. Infra-red and other 3-wire 4-20mA Sensors 3 wire systems indicate that the sensor at the end of the TQ4000 requires power. The TQ4000 can adequately drive up to 3x24Volt sensors each requiring less than 0.25W per sensor.
Product Manual TQ 4000 Modbus Communications The TQ4000 unit features dual channel Modbus communications over 2 serial RS485 lines. This communication allows remote interrogation of the channel concentrations and the status of the channel alarms and fault conditions. It is also possible for remote alarm mute and alarm reset functions to be performed.
Page 53
Modbus Register Addresses For TQ4000 Input Register Starting Starting Number Number Number (0x04) Address(High) Address(Low) Registers(High) Registers(Low) of Bytes Station Number 0x00 0x01 0x00 0x01 Read (0x04) Write (0x10) Channel 1 Conc. 0x00 0x02 0x00 0x01 Channel 2 Conc. 0x00...