Environmental
FieldPoint modules are intended for indoor use only. For outdoor use, they must
be installed in a suitable sealed enclosure.
Operating temperature ...................... – 40 to 70 °C
Storage temperature .......................... –55 to 85 °C
Humidity ........................................... 10 to 90% RH, noncondensing
Maximum altitude............................. 2,000 m; at higher altitudes the isolation
Pollution Degree ............................... 2
Shock and Vibration
Operating vibration
Random (IEC 60068-2-64)......... 10–500 Hz, 5 g
Sinusoidal (IEC 60068-2-6) ....... 10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27).............................. 50 g, 3 ms half sine,
© National Instruments Corporation
voltage ratings must be lowered
rms
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations