Annex; After-Sales Service; Tightening Torques - Samson 2489/58 Series Mounting And Operating Instructions

Pressure-independent control valves flow regulators with electric actuator and control thermostat
Table of Contents

Advertisement

9 Annex

9.1 After-sales service

Contact SAMSON's After-sales Service for
support concerning service or repair work or
when malfunctions or defects arise.
E-mail address
You can reach our after-sales service at
aftersalesservice@samsongroup.com.
Addresses of SAMSON AG and its subsid-
iaries
The addresses of SAMSON, its subsidiaries,
representatives and service facilities
worldwide can be found on our website
(u www.samsongroup.com) or in all
SAMSON product catalogs.
To assist diagnosis and in case of an unclear
mounting situation, specify the following de-
tails (so far as possible). See section 2:
− Device type and valve size
− Model number and configuration ID
− Upstream and downstream pressure
− Temperature
− Min. and max. flow rate
− Is a strainer installed?
− Installation drawing showing the exact
location of the regulator and all the ad-
ditionally installed components (shut-off
valves, pressure gauge etc.)
EB 3135-2 EN

9.2 Tightening torques

Part
Valve size
Coupling nut
(1.2)
Coupling nut (7)
Screw joint with
restriction (11.1)
Screw fitting
(11.2)
Annex
Tightening
torque in Nm
DN 15
200
DN 20
250
DN 25
300
DN 32
400
DN 40
600
DN 50
800
All
20
All
22
All
22
37

Advertisement

Table of Contents
loading