To Install The Outdoor Unit; To Provide Drainage; To Prevent The Outdoor Unit From Falling Over - Daikin SkyAir RZAG35A2V1B Installer's Reference Manual

Hide thumbs Also See for SkyAir RZAG35A2V1B:
Table of Contents

Advertisement

6 Installation
Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.
Fix the unit securely by means of foundation bolts in accordance
with the foundation drawing.
Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field
supply).
(mm)
In any case, provide at least 300  mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100 mm above
the maximum expected level of snow. In this case, it is
recommended to construct a pedestal.
6.3.4

To install the outdoor unit

6.3.5

To provide drainage

▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is proper
drainage in order to avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drain
waste water away from the unit.
▪ Avoid drain water flowing over the footpath, so that it does NOT
become slippery in case of ambient freezing temperatures.
Installer reference guide
12
4× M8/M10
▪ If you install the unit on a frame, install a waterproof plate within
150  mm of the bottom side of the unit in order to prevent water
from getting into the unit and to avoid drain water dripping (see the
following figure).
NOTICE
If the unit is installed in a cold climate, take adequate
measures so that the evacuated condensate CANNOT
freeze.
INFORMATION
For information on the available options, contact your
dealer.
NOTICE
Provide at least 300  mm of free space below the unit.
Additionally, make sure the unit is positioned at least
100 mm above the expected level of snow.
1 Use a drain plug for drainage.
2 Use a Ø16 mm hose (field supply).
a
Drain port
b
Bottom frame
c
Drain plug
d
Hose (field supply)
To close the drain holes and attach the drain
socket
NOTICE
In cold areas, do NOT use a drain socket, hose and caps
(1, 2) with the outdoor unit. Take adequate measures so
that the evacuated condensate CANNOT freeze.
1 Install drain caps 1 and 2 (accessory). Make sure the edges of
the drain caps close off the holes completely.
a
b
a
Bottom frame
b
Drain cap
2 Install the drain socket.
a
b
c
b
b
a
a
a
Drain hole. Install a drain cap (2).
b
Drain hole. Install a drain cap (1).
c
Drain hole for drain socket
6.3.6
To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
b
a
c
d
RZAG35~60A2V1B
R32 split series
4P540076-1A – 2018.11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Skyair rzag50a2v1bSkyair rzag60a2v1b

Table of Contents