UNIT SIZE
003
(2 Tons)
004
(3 Tons)
005
(4 Tons)
006
(5 Tons)
007
(6 Tons)
*Two heater packages required to provide kW indicated.
** Minimum airflow is 350 cfm/ton (1400 cfm) when two CRHEATER004B00 heaters are installed on a 4 ton, 230v heat pump.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kWnew = 16 kW (215/240)2
kWnew = 12.8 kW (rating at 215 v)
Electric Heating Capacitie
Table 3—
VOLTAGE
ACCESSORY
(60 Hz)
(kW)
3.3/4.4
208/230
4.9/6.5
(single phase)
6.5/8.7
7.9/10.5
3.3/ 4.0/ 4.4
4.9/ 5.8/ 6.5
208/230/240
6.5/ 8.0/ 8.7
(single phase)
7.9/ 9.6/10.5
9.8/11.6/13.0*
3.3/ 4.0/ 4.4
4.9/ 5.8/ 6.5
208/230/240
6.5/ 8.0/ 8.7
(3 phase)
7.9/ 9.6/10.5
12.0/14.7/16.0
5.5/ 6.0
460/480
8.1/ 8.8
(3 phase)
10.6/11.5
12.9/14.0
3.3/ 4.0/ 4.4
6.5/ 8.0/ 8.7
208/230/240
9.8/11.6/13.0*
(single phase)
13.1/16.0/17.4*
15.8/19.3/21.0*
4.9/ 5.8/ 6.5
208/230/240
6.5/ 8.0/ 8.7
(3 phase)
12.0/14.7/16.0
15.8/19.3/21.0*
5.5/ 6.0
460/480
10.6/11.5
(3 phase)
12.9/14.0
21.1/23.0*
4.9/ 5.8/ 6.5
6.5/ 8.0/ 8.7
208/230/240
9.8/11.6/13.0*
(single phase)
13.1/16.0/17.4*
15.8/19.3/21.0*
4.9/ 5.8/ 6.5
7.9/ 9.6/10.5
208/230/240
12.0/14.7/16.0
(3 phase)
15.8/19.3/21.0*
19.9/24.3/26.5*
5.5/ 6.0
10.6/11.5
460/480
12.9/14.0
(3 phase)
21.1/23.0*
23.4/25.5*
4.9/ 5.8/ 6.5
7.9/ 9.6/10.5
208/230/240
12.0/14.7/16.0
(3 phase)
15.8/19.3/21.0*
19.9/24.3/26.5*
5.5/ 6.0
10.6/11.5
460/480
12.9/14.0
(3 phase)
21.1/23.0*
23.4/25.5*
s
ACCESSORY HEATER
PART NUMBER
CRHEATER --- ---A00
(or --- ---B00 where indicated)
001
002
003B00
004B00
001
002
003B00
004B00
002 & 002
001
002
003B00
004B00
005
006
007
008
009
001
003B00
002 & 002
003B00 & 003B00
004B00 & 004B00**
002
003
005
004B00 & 004B00**
006
008
009
008 & 008
002
003B00
002 & 002
003B00 & 003B00
004B00 & 004B00
002
004B00
005
004B00 & 004B00
004 & 005
006
008
009
008 & 008
008 & 009
002
004B00
005
004B00 & 004B00
004B00 & 006
006
008
009
008 & 008
008 & 009
2
10
SINGLE POINT BOX
PACKAGE NO.
CRSINGLE --- ---A00
--- ---
--- ---
004
004
--- ---
--- ---
004
004
005
--- ---
--- ---
--- ---
--- ---
002
--- ---
--- ---
--- ---
--- ---
--- ---
004
005
005
005
--- ---
--- ---
002
003
--- ---
--- ---
--- ---
--- ---
004
004
005
005
005
--- ---
002
002
003
002
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
002
002
003
003
--- ---
--- ---
--- ---
--- ---
--- ---