Fault
Type
The fan is
rotating
slowly.
Excessivel
y small
airflow
volume
Vibration
Abnormal
noise
Issue 04 (2022-06-30)
Possible Cause
The fan blade is
blocked or dirty.
The temperature is
too low for the
lubricating grease of
the bearing.
The airflow direction
is incorrect (the
direction of the
motor is opposite to
that of the high-
speed airflow).
The fan does not
rotate.
Fan blade friction/
collision
The active
temperature
management
function is enabled
(when the motor or
electronic system is
overheated).
The fan is rotating
slowly.
The air channel is
blocked.
The pressure loss is
different from the
designed value.
Imbalance
Bearing damage or
wear
Copyright © Huawei Technologies Co., Ltd.
8 System Operation and Maintenance
Solution
Power off the motor and prevent it from
being connected again.
● Check whether the motor is powered off.
● Remove the protective grille.
● Clear foreign matters or contaminants.
● Reinstall the protective grille.
Install the bearing with low-temperature
lubricating grease.
Check the airflow direction (rotation caused
by airflow reversal).
Clear foreign matters or dirt in the fan if
necessary.
Check whether the air circulation is normal.
Clear foreign matters if necessary.
The fan blade is blocked or polluted.
Check the air inlet temperature.
Check the installation space (wind speed on
the heat sink).
Check the fan speed.
Check whether the airflow is smooth (air
intake/exhaust damper and air filter).
The fan blade is blocked or polluted.
Check the selected fan.
Check whether the fan blades are
damaged, polluted, or frozen.
Replace the bearing.