6-4) If defrost does not operate (F/R DEF Heater)

• If defrost has trouble, select the self-diagnostic function to detect the error of defrost heater before Power Off.
(Check the function with the self-diagnostic function.)
F DEF ERROR
R DEF ERROR
** Measuring point of resistance value according to heater**
R-DEF : CN70 "5"(WHT) ↔ CN70 "1" (BLK) measuring resistance
value(132 ohm ± 7%)
F-DEF : CN70 "3"(BLU) ↔ CN70 "1" (BLK) measuring resistance
value(63 ohm + 8%)
** 0Ω: Short trouble / ∞Ω: Open(bimetal, heater) trouble
Reference to the manual "Self-Diagnostic".
** Measuring point of resistance value according to sensor **
R-DEF : CN51 - "12" ↔ "13" measuring resistance value
F-DEF : CN51 - "5" ↔ "7" measuring resistance value
** 0Ω : Short trouble /Ω∞ : Open trouble
Resistance value of sensor according to temperature
86℉(30℃)
4.22kΩ
68℉(20℃)
6.05kΩ
50℉(10℃)
8.87kΩ
32℉(0℃)
13.29kΩ
14℃ (-10℉)
20.42kΩ
-4℉-20℃)
32.23kΩ
-22℉(-30℃)
52.41kΩ
Recheck the applicable sensor.
Reference
If defrost sensor temperatures of fresh food
and freezer compartments are higher than
50℉(10℃), 53.6℉(12℃) by the heating from
heater, heating would be finished and will
return to cooling operation after a pause.
☞ Checking method of F DEF Heater resistance value
F-DEF : CN70 "3"(BLU) ↔ CN70 "1" (BLK)
R-DEF : CN70 "5"(WHT) ↔ CN70 "1" (BLK)
- Recheck if resistance values are different after the test
1) F DEF Heater
2) R DEF Heater
This document cannot be used without Samsung's authorization.
If you need the
Manual defrosting of fresh food and
temperature with
detail, refer to DATA1.
temperature
table
No
PIN Number
Start
Are the all deforst
heater normal?
Yes
Is defrost sensor by
self-diagnostic normal?
Yes
Is the temperature
of defrost sensor lower than
53.6℉(12℃)?
Yes
freezer compartments
operate simultaneously.
Is power applied to
each defrost heaters?
Yes
Does the system
return to cooling operation
after heating for specified
time?
Yes
Normal
Is connection
terminal of MAIN PBA part
normal?
Yes
Check bimetal, heater itself,
disconnection etc.
Replace failure Relay or
replace PCB ASS'Y.
92
No
Check the bimetal, heater disconnection,
wiring connection etc.
Refer to self-diagnostic
function in the manual.
No
Replace the applicable sensor
No
Manual operation for a certain time.
Refer to TEST Mode Entering
No
No
Repair connection terminal.