Heatstore HSACR3000N Installation, Operation And Maintenance Instructions

Heatstore HSACR3000N Installation, Operation And Maintenance Instructions

Warm air curtain heaters

Advertisement

Quick Links

Avon Riverside, Victoria Road, Avonmouth, Bristol BS11 9DB
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR
WARM AIR CURTAIN HEATERS
MODELS
These units are 990mm 3kW & 4.5kW modular recessed
heaters designed for mounting above doorways and similar
entrances to fit directly into a 600 mm grid in a suspended
ceiling, and may be used as space heaters. (Minimum ceiling
height of 2.2m: maximum height 2.8m).
MOUNTING
When fitting ensure that the air discharge is situated as close
to the door as possible.
designed to fit directly into any suspended ceiling, especially
ceiling tile grid formation. If the grid does not align with the
door then it will need modifying.
Telephone: 0117 923 5375
Catalogue Numbers HSACR3000N & HSACR4500N
PLEASE RETAIN THIS LEAFLET FOR FUTURE MAINTENANCE
The recessed air curtains are
Fax: 0117 923 5374
The unit should be mounted so that the airflow is not obstructed by
any part of the doorframe.
INSTALLATION
Each unit is provided with 2 brackets with 4 x M6 inserts (2
either end) to allow the unit to be suspended via threaded
rods or wire ties. Please note, when fixing using threaded
rods or wire ties (not supplied) that a suitable structure must
be used ensuring that it can maintain the unit weight.
Ensure that locking nuts are fitted to stop the threaded
bar/wire ties rotating and coming away from the casing. For
dimensions of fixing centres please see figure 1.
41000931 iss 01

Advertisement

loading

Summary of Contents for Heatstore HSACR3000N

  • Page 1 Fax: 0117 923 5374 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR WARM AIR CURTAIN HEATERS Catalogue Numbers HSACR3000N & HSACR4500N PLEASE RETAIN THIS LEAFLET FOR FUTURE MAINTENANCE MODELS The unit should be mounted so that the airflow is not obstructed by any part of the doorframe.
  • Page 2 ELECTRICAL CONNECTIONS CONTROLS These units are suitable for connection to a 230/240 Volt 50 Hz To switch on the appliance and operate the blower, depress the single-phase AC supply. The heaters consume 3kW, 4.5kW left-hand switch with a control light (marked “FAN”). respectively at 240 volts when switched to the full heat position.