9.3.2 How to Calculate System Current Load
Use Table 9.3 on page 131 to calculate current load as follows:
1.
Enter the quantity of devices in all three columns.
2.
Enter the current draw where required. Refer to the Device Compatibility Document and SWIFT Manual for compatible devices and
their current draws.
3.
Calculate the current draws for each in all columns.
4.
Sum the currents for each column. This is the total load.
5.
Verify that the total from Column 1 is less than or equal to the value specified in the note.
6.
Copy the totals from Column 2 and Column 3 to Table 9.4 on page 132.
Table 9.3 contains columns for calculating current load. For each column, calculate the current and enter the total (in amperes) in the bottom
row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 9.4 on page 132. For maximum output
current available per circuit and per panel, refer to Section 1.2, "Specifications", on page 14.
Device Type
1
Main Circuit Board
CLSS Pathway Pro
1
Main board with display only.
The following is the minimum configuration to meet the NFPA requirements.
(pre-installed CLSS Pathway Pro)
Where Y = Yes, N = No, and O = Optional
1
Non-Emergency
2
Also required when devices for Carbon Monoxide signaling are employed
Supplement for ES-200XP Applications — P/N LS10387-000FL-E:A 2/23/2023
Calculation Column 1
Primary (AC) Power Source
Fire Alarm Current (amps)
Qty
X [current draw]=
[
]
X[0.100]=
Table 9.3 System Current Load Calculations
Appendix H: NFPA Requirements
Module
ES-200XP
HW-AV-LTE-M-FL
Calculation Column 2
Secondary (Battery) Power Source
Fire Alarm Current (amps)
Total
Qty
X [current draw]=
1
X[0.257]=
[
]
X[0.100]=
Local
Aux
RS
Y
Y
Y
Y
Y
Y
Calculation Column 3
Secondary (Battery) Power Source
Standby Current (amps)
Total
Qty
X [current draw]=
1
X[0.141]=
[
]
X[0.100]=
Process
CS
Proprietary
Management
Y
N
2
Y
N
Total
1
Y
Y
9