FXZQ_TBVJU
10. Capacity Tables
10.1 Cooling Capacity at Te: 43°F (6°C)
61 (16.1)
Model
TC
MBH
FXZQ05TBVJU
4.7
FXZQ07TBVJU
6.1
FXZQ09TBVJU
7.6
FXZQ12TBVJU
9.5
FXZQ15TBVJU
11.9
FXZQ18TBVJU
14.3
TC: Total capacity: MBH
SHC: S ensible heat capacity: MBH
Note:
1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system satisfies
the required heat load.
2.
shows rated condition.
10.2 Heating Capacity
62 (16.7)
Model
TC
MBH
FXZQ05TBVJU
7.2
FXZQ07TBVJU
9.3
FXZQ09TBVJU
11.6
FXZQ12TBVJU
14.6
FXZQ15TBVJU
18.5
FXZQ18TBVJU
21.7
TC: Total capacity: MBH
Note:
1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system satisfies
the required heat load.
2.
shows rated condition.
Indoor air temp. °FWB (°CWB) (Te: 43°F (6°C))
64 (17.8)
SHC
TC
SHC
MBH
MBH
MBH
4.3
5.2
4.7
5.0
6.9
5.7
6.0
8.4
6.6
6.9
10.9
7.8
9.5
13.5
10.4
11.4
16.0
12.5
Indoor air temp. °FDB (°CDB) (Tc: 115°F (46°C))
65 (18.3)
TC
MBH
7.2
9.2
11.4
14.5
18.3
21.6
67 (19.4)
70 (21.1)
TC
SHC
TC
MBH
MBH
MBH
5.8
4.7
6.0
7.5
5.5
7.9
9.5
6.6
9.9
12.0
7.8
12.5
15.0
10.8
15.7
18.0
13.0
18.7
68 (20.0)
70 (21.1)
TC
TC
MBH
MBH
6.9
6.5
8.9
8.5
10.9
10.5
13.9
13.5
17.7
17.0
20.7
20.0
15
72 (22.2)
SHC
TC
SHC
MBH
MBH
MBH
4.5
6.0
4.3
5.3
8.0
5.3
6.4
9.9
6.2
7.6
12.7
7.4
10.4
16.1
10.1
12.8
18.9
12.5
72 (22.2)
TC
MBH
6.5
8.1
10.1
12.8
16.6
19.3
EDUS392209-F9
75 (23.9)
TC
SHC
MBH
MBH
6.3
4.0
8.0
5.0
10.2
5.9
13.0
7.2
16.3
9.8
19.4
12.3
C: CA17A794
75 (23.9)
TC
MBH
6.2
7.8
9.6
12.2
15.7
18.2