40MBAB: Installation Instructions
External Static
Capacity
Pressure
Range
40MBABQ30XA3
0 - 0.80 in. w.g.
40MBABQ36XA3
0 - 0.80 in. w.g.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Electric Heater Nominal Air Flow Settings (Sheet 2 of 3)
Electric
Fan Speed
Heater Kit
Cooling Turbo
—
Cooling High
—
Cooling Medium
—
Cooling Low
—
Heat Pump Turbo
—
Heat Pump High
—
Heat Pump
—
Medium
Heat Pump Low
—
Auxiliary Heater
15KW
Default 0
15KW,
Auxiliary Heater 1
10KW
10KW,
Auxiliary Heater 2
8KW
Auxiliary Heater 3
5KW
Cooling Turbo
—
Cooling High
—
Cooling Medium
—
Cooling Low
—
Heat Pump Turbo
—
Heat Pump High
—
Heat Pump
—
Medium
Heat Pump Low
—
Auxiliary Heater
20KW
Default 0
Auxiliary Heater 1
15KW
10KW,
Auxiliary Heater 2
8KW
8KW,
Auxiliary Heater 3
5KW
24V Thermostat
24V
DIP Switch
DIP Switch
Terminal
Engaged
SW3-4=ON
Y2/Y
SW3-4=OFF
Y2/Y
—
Y1
—
—
—
—
—
B+Y2/Y, W
—
Y1
—
—
SW4-1=OFF
SW4-1=OFF
SW4-2=OFF
W1, W2, AUX
SW4-2=OFF
SW4-3=OFF
SW4-3=OFF
SW4-1=OFF
SW4-1=OFF
SW4-2=OFF
W1, W2, AUX
SW4-2=OFF
SW4-3=ON
SW4-3=ON
SW4-1=OFF
SW4-1=OFF
SW4-2=ON
W1, W2, AUX
SW4-2=ON
SW4-3=OFF
SW4-3=OFF
SW4-1=OFF
SW4-1=OFF
SW4-2=ON
W1, W2, AUX
SW4-2=ON
SW4-3=ON
SW4-3=ON
SW3-4=ON
Y2/Y
SW3-4=OFF
Y2/Y
—
Y1
—
—
—
—
—
B+Y2/Y, W
—
Y1
—
—
SW4-1=OFF
SW4-1=OFF
SW4-2=OFF
W1, W2, AUX
SW4-2=OFF
SW4-3=OFF
SW4-3=OFF
SW4-1=OFF
SW4-1=OFF
SW4-2=OFF
W1, W2, AUX
SW4-2=OFF
SW4-3=ON
SW4-3=ON
SW4-1=OFF
SW4-1=OFF
SW4-2=ON
W1, W2, AUX
SW4-2=ON
SW4-3=OFF
SW4-3=OFF
SW4-1=OFF
SW4-1=OFF
SW4-2=ON
W1, W2, AUX
SW4-2=ON
SW4-3=ON
SW4-3=ON
25
Wired Controller
Air Volume CFM
Mode
—
Cool
—
Cool
—
Cool
—
Cool
—
Heat
—
Heat
—
Heat
—
Heat
Heat + AUX, AUX
Heat + AUX, AUX
Heat + AUX, AUX
Heat + AUX, AUX
—
Cool
—
Cool
—
Cool
—
Cool
—
Heat
—
Heat
—
Heat
—
Heat
Heat + AUX, AUX
Heat + AUX, AUX
Heat + AUX, AUX
Heat + AUX, AUX
988
894
806
712
918
876
665
453
1088
1029
976
918
1188
1082
971
865
1112
1059
794
582
1306
1241
1176
1112