Auto-Reclosure Indications In Monitor Direction - ABB Relion 615 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 3
Interoperability profile for 615 series IEC 60870-5-103
3.3.3.6
40
<66>
Start /pick-up L
<67>
Start /pick-up N
<68>
General trip
<69>
Trip L
1
<70>
Trip L
2
<71>
Trip L
3
<72>
Trip I>> (back-up operation)
<73>
Fault location X in ohms
<74>
Fault forward/line
<75>
Fault reverse/busbar
<76>
Teleprotection signal transmitted
<77>
Teleprotection signal received
<78>
Zone 1
<79>
Zone 2
<80>
Zone 3
<81>
Zone 4
<82>
Zone 5
<83>
Zone 6
<84>
General start/pick-up
<85>
Breaker failure
<86>
Trip measuring system L
<87>
Trip measuring system L
<88>
Trip measuring system L
<89>
Trip measuring system E
<90>
Trip I>
<91>
Trip I>>
<92>
Trip IN>
<93>
Trip IN>>
Note: Function-specific fault signals are as default mapped to private data locations in 615 series IEDs.

Auto-reclosure indications in monitor direction

INF
Semantics
<128>
CB 'on' by AR
<129>
CB 'on' by long-time AR
<130>
AR blocked
Note <129>: Terms 'short-' or 'long-time' AR are not directly usable in 615 series. The AR
functionality in the IED performs AR shots (1..5) that are user configurable. See private AR data
definitions. Depending on user AR configuration it is possible to re-map some private data into
standard data, if wanted.
3
1
2
3
1MRS756883 C
RET615
Point List Manual