Section 2
IEC 60870-5-103 data mappings
34
IEC 61850 name
.Tmp.mag
.TmpRl.mag
LD0.CMSTA1 Demand currents (1)
LD0.CMSTA1
.AvAmpsA.mag
.AvAmpsB.mag
.AvAmpsC.mag
LD0.CMSTA2 Demand currents (2)
LD0.CMSTA2
.AvAmpsA.mag
.AvAmpsB.mag
.AvAmpsC.mag
LD0.VMMXU1 Voltage measurands (1)
LD0.VMMXU1.phV
.phsA.cVal.mag
.phsB.cVal.mag
.phsC.cVal.mag
LD0.VMMXU1.PPV
.phsAB.cVal.mag
.phsBC.cVal.mag
.phsCA.cVal.mag
LD0.VSMSQI1 Sequence of voltages (1)
LD0.VSMSQI1
.SeqA.c1.cVal.mag
.SeqA.c2.cVal.mag
.SeqA.c3.cVal.mag
LD0.PEMMXU1 Power measurands (1)
LD0.PEMMXU1
.TotW.instMag
.TotVAr.instMag
.TotVA.instMag
.TotPF.instMag
LD0.TR2PDIF1 Transformer Differential- and Bias currents (1)
LD0.TR2PDIF1.DifAClc
.phsA.cVal.mag
.phsB.cVal.mag
.phsC.cVal.mag
LD0.TR2PDIF1.RstA
.phsA.cVal.mag
Table continues on next page
Description
Temperature
Relative temperature
Phase-current demands
-phsA magnitude
-phsB magnitude
-phsC magnitude
Phase-current demands
-phsA magnitude
-phsB magnitude
-phsC magnitude
Phase-to-ground voltage
-phsA magnitude
-phsB magnitude
-phsC magnitude
Phase-to-phase voltage
-phsAB magnitude
-phsBC magnitude
-phsCA magnitude
Sequence of voltages
-positive magnitude
-negative magnitude
-zero magitude
Active power P value
Reactive power Q value
Apparent power S value
Power factor value
Differential current A
Differential current B
Differential current C
Bias current A
1MRS756883 C
Scale
ix (T-a) xi (T-b)
1000
12
12
1000
-
-
2.4
13*
27*
2.4
14*
28*
2.4
15*
29*
2.4
16*
30*
2.4
17*
31*
2.4
18*
32*
2.4
13
2.4
14
2.4
15
2.4
16
2.4
17
2.4
18
2.4
20
2.4
21
2.4
22
1000
23
1000
24
1000
25
1
26
1.2
19*
33*
1.2
20*
34*
1.2
21*
35*
1.2
22*
36*