Technical Data - S+S Regeltechnik Premasgard SHD Operating Instructions, Mounting & Installation

Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
®
PREMASGARD
  SHD
The pressure measuring transducer PREMASGARD
pressure into standard signals of 0 -10 V or 4...20 mA. Process connection is G 1 ⁄ 2" straight external pipe thread. PREMASGARD
is used for pressure measurement in gaseous and liquid media. Applications of this pressure transmitter are in hydraulics, pneumatics,
process technology, in mechanical and plant engineering. The stainless steel membrane is absolutely vacuum-tight.
TECHNICAL DATA:
Power supply: .............................. 24 V AC for output 0 –10 V
Measuring ranges: ..................... see table
Output signal: .............................. 0 -10 V 3-wire, working resistance R
Electrical connection: ................ 0.14 - 1.5 mm², via terminal screws inside
Pressure connection: ................ pipe thread G 1 ⁄ 4", including adapter for G 1 ⁄ 2"
Type of pressure: ....................... relative
Measuring principle: .................. thin-film, piezo-resistive on steel membrane
Temperature of medium: .......... - 40 ... +100 °C
Mounting: ..................................... directly on pressure line
Enclosure: .................................... stainless steel
Connecting head: ....................... plastic, ca. 98 x 50 x 34 mm
Medium contacting parts: ........ stainless steel 1.4301 X 5 CrNi 18-10,
Response time: ........................... 1.5 ms
Class: ............................................ 0.5 %
Total error: .................................. < 3 %
Overload range: .......................... 2 times measuring range, final value (FS)
Bursting pressure: ..................... 3 times measuring range, final value (FS)
Insulating resistance: ................ ≥ 100 MOhm, at 20 °C (500 V DC)
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529)
Standards: ................................... CE conformity, electromagnetic compatibility
Connecting diagram
1
Output pressure 0-10V
3
Supply voltage UB+ 24V AC
UB- GND
2
Type ⁄ WG1 
Measuring Range 
SHD-U 1
0 ...1bar
SHD-U 2.5
0 ... 2.5 bar
SHD-U 6
0 ... 6 bar
SHD-U 10
0 ...10 bar
SHD-U 16
0 ...16 bar
SHD-U 25
0 ... 25 bar
SHD-U 40
0 ... 40 bar
®
SHD measures relative pressures in the bar range. It converts the measurand
12 – 32 V DC for output 4...20 mA,
R
depending on working resistance
L
(other ranges upon request)
4 ... 20 mA 2-wire, working resistance
R
(Ohm) = (UB (V) -10 V) ⁄ 0.02 A
A
right angle plug connector shape C
straight external pipe thread (other connections on request)
O rings, no silicone oil
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
SHD - U
Output
0 -10 V
0 -10 V
0 -10 V
0 -10 V
0 -10 V
0 -10 V
0 -10 V
≥ 2 kΩ or
A
Connecting diagram
3
Supply voltage UB+ 24V DC
2
Output pressure 4-20mA
Type ⁄ WG1 
SHD - I 1
SHD - I 2.5
SHD - I 6
SHD - I 10
SHD - I 16
SHD - I 25
SHD - I 40
Measuring Range 
Output
0 ...1.0 bar
4 ... 20 mA
0 ... 2.5 bar
4 ... 20 mA
0 ... 6.0 bar
4 ... 20 mA
0 ...10 bar
4 ... 20 mA
0 ...16 bar
4 ... 20 mA
0 ... 25 bar
4 ... 20 mA
0 ... 40 bar
4 ... 20 mA
®
SHD
SHD - I

Hide quick links:

Advertisement

Table of Contents
loading