Technical Data - S+S Regeltechnik Hygrasreg RH-30 Operating Instructions, Mounting & Installation

Room hygrostats and humidity sensors
Hide thumbs Also See for Hygrasreg RH-30:
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
®
HYGRASREG
RH - 30
Electronic room hygrostats and humidity sensors HYGRASREG
two switching outputs, adjustable switching thresholds, with or without an optional display for
displaying ACTUAL humidity (accuracy class ± 3 % r.H.) and for setting the target humidity.
They are used to control and monitor the relative humidity, e.g. in ventilation and air conditioning
ducts, laboratories, production facilities, climatic test cabinets, indoor swimming pools, green-
houses, etc. to control humidifying and dehumidifying equipment. These measuring transducers are
designed for exact humidity measurement. RH-30 uses a digital long-term stable sensor as a
measuring element for humidity measurement. Applications in dust-free, pollutant-free, non-
aggressive air.

TECHNICAL DATA

Power supply:
Power consumption:
Sensors:
Setting range:
Operating difference:
Output:
Deviation, humidity:
Ambient temperature:
Long-term stability:
Enclosure:
Enclosure dimensions:
Installation:
Protection class:
Protection type:
Electrical connection:
Standards:
Optional:
F UN C T I O N
Humidifying:
Dehumidifying:
®
HYGRASREG
RH - 30 – Room hygrostats and humidity sensors (± 3 %)
Type ⁄ WG02
Setting Range
Humidity
RH - 30
R H - 3 0 W
5...95 % r. H.
R H - 3 0 W_ D I S P L AY
5...95 % r. H.
RH - 30 - U
R H - 3 0 W U
5...95 % r. H.
®
RH-30 with one continuous and
24 V AC (± 20 %); 15...36 V DC (± 10 %)
< 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
digital humidity sensor,
low hysteresis, high long-term stability
5...95 % r. H.
(switch steps 1 and 2 are separately adjustable)
Mode 1: both switch steps are arbitrary adjustable
Mode 2: 5 % between both switch steps
(adjustable via DiP switches)
potential-free changeover contacts
(2 x changeover contact 24 V,
separately adjustable, 1x 0 - 10 V ^ = 0 - 100 % r. H.)
± 3 % r. H. (20...80 %); at + 20 °C, otherwise ± 5 % r. H.
storage –35...+85 °C;
operation – 30...+75 °C, non-precipitating
± 1 % per year
plastic, material ABS, colour pure white (similar to RAL 9010)
98 x 98 x 35 mm (Baldur 2)
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4-hole for mounting on vertically or horizontally installed in-wall flush boxes
for cable entry from the back, with predetermined breaking point for on - wall cable entry
from top ⁄ bottom in case of plain on - wall installation
III (according to EN 60 730)
IP 30 (according to EN 60 529)
0.14 - 1.5 mm
2
, via terminal screws
CE conformity, EMC directive 2004 ⁄ 108 ⁄ EC
two-line display with illumination, cutout approx. 36 x15 mm (W x H),
for displaying ACTUAL humidity respectively for humidity setpoint adjustment
1st step: wire contacts 11 - 12.
When actual humidity falls more than 3 % r. H. (hysteresis) below switching threshold S1,
changeover contact switches to 11 - 12.
2nd step: wire contacts 21 - 22.
When actual humidity falls more than 3 % r. H. (hysteresis) below switching threshold S 2,
changeover contact switches to 21 - 22.
Terminal 2: Output Humidity ^ = 0 - 100 % r. H.
1st step: wire contacts 11 - 13.
When actual humidity exceeds switching threshold S 1, changeover contact switches to 11 - 13.
2nd step: wire contacts 21 - 23.
When actual humidity exceeds switching threshold S 2, changeover contact switches to 21 - 23.
Terminal 2: Output Humidity ^ = 0 - 100 % r. H.
Output
2 x Changeover contact, 1x 0 -10 V
2 x Changeover contact, 1x 0 -10 V
2 x Changeover contact, 1x 0 -10 V
Connecting diagram
1
2
3
12
11
13
22
21
23
Steps
Display
Item No.
External setting
two-step
1202-30B6-1011-200
two-step
1202-30B6-1211-200
Internal setting
two-step
1202-30B6-1021-200
Rev. 2016 - V20 GB
RH - 30 - U
+UB 24V AC/DC
Output humidity 0-10V
in % r.H.
–UB GND
Humidifying
Relay 1
Dehumidifying
Humidifying
Relay 2
Dehumidifying
Potential-free
changeover contact 24V

Advertisement

Table of Contents
loading

Table of Contents