G
®
PREMASGARD
  SHD - LC
The pressure measuring transducer PREMASGARD
pressure into standard signals of 0 -10 V or 4...20 mA. Process connection is G 1 ⁄ 2" straight external pipe thread. PREMASGARD
is used for pressure measurement in gaseous and liquid media. Applications of this pressure transmitter are in hydraulics, pneumatics,
process technology, in mechanical and plant engineering.
Not applicable for ammonia and Freon !
TECHNICAL DATA:
Power supply: .............................. 15 - 33 V DC for output 0 -10 V
Measuring ranges: ..................... see table
Output signal: .............................. 0 -10 V 3-wire, working resistance R
Electrical connection: ................ 0.14 - 1.5 mm², via terminal screws inside
Pressure connection: ................ G 1 ⁄ 2" A, straight external pipe thread sealing at the back,
Type of pressure: ....................... relative
Measuring principle: .................. thin-film, piezo-resistive on ceramic measuring cell
Temperature of medium: .......... - 15 ... + 80 °C
Mounting: ..................................... directly on pressure line
Pressure connection: ................ stainless steel 1.4305
Connecting head: ....................... plastic, ca. 130 x 50 x 36 mm
Medium contacting parts: ........ stainless steel 1.4305, ceramics, sealing material (Viton)
Load changes: ............................. < 50 Hz
Response time: ........................... < 5 ms
Class: ............................................ ± 0.5 %
Total error: .................................. < 3 %
Overload range: .......................... 2 times measuring range, final value (FS)
Bursting pressure: ..................... 3 times measuring range, final value (FS)
Insulating resistance: ................ ≥ 100 MOhm, at 20 °C (500 V DC)
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529) with receptacle mounted
Standards: ................................... CE conformity, electromagnetic compatibility
Connecting diagram
1
Supply voltage UB+ 24V DC
GND
3
2
Output pressure 0-10V
Type ⁄ WG1 
Measuring Range 
SHD - LC - U 6
0 ... 6 bar
SHD - LC - U 10
0 ...10 bar
SHD - LC - U 16
0 ...16 bar
®
SHD-LC measures relative pressures in the bar range. It converts the measurand
10 - 33 V DC for output 4 ... 20 mA,
R
depending on working resistance
L
4 ... 20 mA 2-wire, working resistance
R
(Ohm) ≤ (UB (V) -10 V) ⁄ 0.02 A
A
right angle plug connector DIN EN 175301- 803 - A
manometer connection (other connections on request)
according to EN 55022,
EN 50081-1 ⁄ - 2, EN 50082 - 2,
EMC directive 2004 ⁄ 108 ⁄ EC
SHD - LC - U
Output
0 -10 V
0 -10 V
0 -10 V
≥ 10 kΩ or
A
Connecting diagram
1
Supply voltage UB+ 24V DC
Output pressure 4-20mA
2
Type ⁄ WG1 
SHD - LC - I 6
SHD - LC - I 10
SHD - LC - I 16
Measuring Range 
Output
0 ... 6 bar
0 -10 V
0 ...10 bar
0 -10 V
0 ...16 bar
0 -10 V
®
SHD-LC
SHD - LC - I