7. SETTINGS
- Parameters:
Sensor parameters
Default value Modifiable parameters
Time delay
15 mn
Sensitivity
PIR (very high)
Daylight setpoint
500 lux
Auto on/Auto
Inactive
off
Walkthrough
Active
Manual on/
Inactive
Auto off
Initial
PIR
Maintain
PIR
Retrigger
PIR
Alert
Inactive
Calibration
Light regula-
Active
tion
Provision of
Auto
light
Time delay: Time for which light is switched on following detection.
Sensitivity: Detector range setting.
Daylight setpoint: Brightness value below which the light is switched
on and above which the light is switched off.
Auto on/Auto off mode:
The light is switched on automatically:
- When presence is detected, if the natural brightness is too low.
The light is switched off automatically:
- Where no presence is detected and at the end of the time delay set.
- Or if there is a sufficient level of natural light (activated setting).
Any new detection causes an automatic switch on if there is insufficient
light.
Walkthrough:
- If there is no presence detected in the 3 minutes following an initial
detection, the product will cut off after 3 minutes.
- If a new presence is detected in the 3 minutes following the initial
detection,
the device will cut off at the end of the time delay set.
Manual on/Auto off mode:
Comes on via a manual switch, automatic switch off:
- Where no presence is detected and at the end of the time delay set.
Following switch off, any new detection within a 30-second period will
cause the device to be switched on automatically.
After 30 seconds the device is switched on via a manual switch.
Initial detection: Light switched on from first detection.
Maintain: The load remains active if any new presence is detected.
Technical data sheet: S000100487EN_2
CONTENTS
Configuration
tools
088230
088235
3,5,10,15,20 mins
0 - 59 mins 59 secs
Low, medium, high, very
high
20, 100, 300, 500, 1000
lux
0 - 1275 lux
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Non-modifiable
Non-modifiable
PIR/Disabled
Enabled/Disabled
0 - 99995 lux
Enabled/Disabled
Auto - 1275 lux
Updated: 26/01/2023
7. SETTINGS (continued)
Retrigger: Function allowing automatic start of the product at the end
of 30 seconds following the load being switched off.
Upon being switched off, any new detection within a 30-second period
will cause the device to be switched on automatically.
After 30 seconds the device must be switched on manually.
Calibration: The surrounding level of light measured with a luxmeter
will then have to be transmitted to the detector.
Light regulation: Light switched off automatically 10 minutes after
the Daylight setpoint has been exceeded. If the light level is below the
Daylight setpoint, the light is activated automatically after 20 seconds.
Provision of light: Quantity of additional lux provided when the light
is switched on.
- Modification of the parameters by the configuration tools
• 0 882 40: Configuration gateway and Legrand Close Up application.
The Close Up application is available on the Apple Store and the Play
Store
App Store
The detector functions are controlled by a number of parameters which
can be changed or programmed by an infrared configurator.
In combination with configuration tool 0 882 40, the Legrand Close Up
smartphone app can be used to view and modify all the detector
parameters with online help.
Point the infrared configuration tool at the detector and send the
necessary programming commands to the unit as indicated in the table
below.
For more information about setting parameters, refer to the data sheet
for the configuration gateway Cat. No. 0 882 40.