Download Print this page
LEGRAND 0 488 07 Manual

LEGRAND 0 488 07 Manual

Pir detector switch

Advertisement

Quick Links

PIR detector switch
1. USE
This device automatically controls a light source by detecting movement
in its supervision zone.
360° detection angle motion detector
Detection type: infra-red (PIR)
Mounting: ceiling
2. TECHNICAL CHARACTERISTICS
Voltage: 100-240 V~
Frequency: 50 / 60 Hz
No-load power consumption: 0,4W
Output by normally open contact connected to phase
Wiring: 2 x 2.5 mm
2
Flush-mounting diameter: 65 mm without flush-mounting box,
68 mm with flush-mounting box
Weight: 114 g
Impact resistance: IK04
Penetration by solid bodies and liquids: IP41 installed product.
Operating temperature: -5°C to +45°C
Storage temperature: -20°C to +70°C
Cover removed
Green detection
indicator light
PIR transmission LED
(for configuration tool)
PIR Detector
230 V~
2000 W
8,5 A
110 V~
1000 W
8,5 A
Incandescent lamp
Halogen lamp
Halogen lamp with separate ferromagnetic or electronic transformer
Fluorescent tubes
Technical data sheet: S000100487EN_2
128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex
Tel : 0 (+33) 5 55 06 87 87 Fax : 0 (+33) 5 55 06 88 88
www.legrand.com
Green programming
indicator light
LEARN key
PIR reception LED
(for configuration tools
or remote control)
Protective shield
2000 W
8,5 A
1000 VA
4,3 A
1000 W
8,5 A
500 VA
4,3 A
Updated: 26/01/2023
CONTENTS
1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . .1
3. Overall Dimensions . . . . . . . . . . . . . . . . . . . . .1
4. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
5. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
6. Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
7. Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
8. Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . .4
9. Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
10. Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3. OVERALL DIMENSIONS
Without protective cover
50
With protective cover
65
10x(2x36 W)
4,3 A
500 VA
5x(2x36 W)
4,3 A
250 VA
Compact fluorescent lamp with integrated ballast
Compact fluorescent lamp with separate ferromagnetic or electronic ballast
Contactors
Catalogue Number(s): 0 488 07
52
82
2,1 A
1000 VA
4,3 A
I max. ≤ 2A
2,1 A
500 VA
4,3 A
Created: 18/05/2010
Page
1/4

Advertisement

loading

Summary of Contents for LEGRAND 0 488 07

  • Page 1 Tel : 0 (+33) 5 55 06 87 87 Fax : 0 (+33) 5 55 06 88 88 www.legrand.com PIR detector switch Catalogue Number(s): 0 488 07 CONTENTS Page 1. Use ........1 2.
  • Page 2: Installation

    PIR detector switch Catalogue Number(s): 0 488 07 4. CONNECTION 5. INSTALLATION Number of terminals: 4 0.3 to 30 mm Terminal type: automatic Ø 65 Terminal capacity: 2 x 2.5 mm Ø 68 Stripping length: 8 mm Cabling with auxiliary control : Manual on/Auto off ...
  • Page 3 In combination with configuration tool 0 882 40, the Legrand Close Up smartphone app can be used to view and modify all the detector Time delay: Time for which light is switched on following detection.
  • Page 4 PIR detector switch Catalogue Number(s): 0 488 07 7.  SETTINGS (continued) 8.  PERFORMANCE (continued) - Modifying the parameters using the configuration tools (continued) Sensitivity Sensitivity • 0 882 30: Configuration tool Low (25%) Medium (50%) When the sensor receives an IR command via a configuration tool, Ø...
  • Page 5 PIR detector switch Catalogue Number(s): 0 488 07 Technical data sheet: S000100487EN_2 Updated: 26/01/2023 Created: 18/05/2010 CONTENTS...