Section 1 Getting Started The Chromalox 3101 is a compact 1/4 DIN program- mable high/low limit controller with two independent alarms. While designed to be low-cost, the 3101 has many features of high-end limit controllers: • Universal Sensor Input • Switching Power Supply allows universal AC voltage input (100 to 230 Vac) •...
RS422/485 Digital Communications and Alarm #2 Relay—Form C contact, 5A @ 120 or 230 Vac RS232 Digital Communications and Alarm #2 Relay—Form C Contact, 5A @ 120 or 230 Vac Code Power Supply 100 - 230 Vac 3101 - Typical Model Number...
Temperature extremes and excessive moisture can damage the instrument. Switch The 3101 has up to seven (7) hardware switches Settings located on the bottom of the controller. The switches are accessible through cutouts in the...
Page 9
Figure 2.3. 2. Place the controller through the square panel cutout and replace the mounting clip. 3. Tighten the mounting clip screw (do not overtighten) to secure the controller fi rmly against the mounting surface. Chromalox 3101 Operator's Manual...
Figure 2.2 Mounting Dimensions (96) (19) (102) (92) (96) (92) (90) Panel Cutout Measurements are shown in inches. Millimeters are shown in parentheses. Figure 2.3 Mounting Diagram Mounting Hole Mounting Clip Mounting Tab Panel Cutout Chromalox 3101 Operator's Manual...
Page 11
Electrical noise can affect the function of any control system. When driving a contactor coil or other inductive load, an appropriately rated AC snubber circuit is recommended (Chromalox Part. No. 0149-01305), as described on page 11, “Re- lay Output Wiring.”...
Figure 2.5. • Three wire RTDs are recommended for greatest accuracy. • Standard shielded copper wire is recommended for RTD extensions. Chromalox 3101 Operator's Manual...
Chromalox recommends 3-wire RTDs for greatest accuracy, and standard shield- ed copper wire for RTD extensions. Make 3-wire RTD connections to terminals 7, 8 and 9 as shown in Figure 2.6 on the following page. Chromalox 3101 Operator's Manual...
It is also necessary to jumper terminals 8 and 9 on the instrument to complete a 2-wire hookup. Figure 2.7 3101 2-Wire Connections Current/Voltage Inputs Figure 2.8 3101 Current Input Wiring (Self-powered) 4-20mA Chromalox 3101 Operator's Manual...
Figure 2.9 3101 Voltage Input Wiring 1-5 Vdc (Self-powered) 0-5 Vdc The 3101 has a +24 Vdc power supply which can be used to power a 4-20mA transmitter. Figure 2.10 3101 Current +24 Vdc Input Wiring 4-20mA (Loop-powered by controller)
Output The 3101 is supplied with: Wiring • 1 Relay Output for Limit Output Control • 1 Relay Output for Alarm #1 As an option, it may also include: • 1 Relay Output for Alarm #2 ☛ Warning Incorrect output wiring may cause system/pro- cess damage.
Figure 2.14. Figure 2.14 Alarm #2 Output 3101 Load AC Neutral Normally Open Fuse* Alarm #2 120 or 230 Vac Normally Closed Load AC Neutral * Fuse should be sized for the current of Alarm #2 Output. Chromalox 3101 Operator's Manual...
Normal Display Mode. Disable Lower Display The lower display may be disabled for applica- tions where it is desirable to have only the Pro- cess Variable displayed in the upper display. See SET PAGE, menu LDSP, page 24. Chromalox 3101 Operator's Manual...
• Scrolls through MENUs in Setup Mode VIEW DATA • In Normal Display Mode, pushbuttons adjust Setpoint. Pushbutton • To access Display Page • In Setup Mode, pushbuttons increase/decrease MENU • To scroll through Display values. Page Menus Chromalox 3101 Operator's Manual...
PAGE/MENU All control parameters, selections and calibration Setup procedures for the 3101 are accomplished through simple MENU selections. These MENU selections are organized into PAGES. On each PAGE you will fi nd a specifi c set of related functions. This organization allows you to go directly to the parameter to be adjusted, without stepping through a long series of unrelated entries.
Page 23
MENU will appear on the upper display, and the current value will appear in the lower display. AL 1 ALO1 AHI1 ➮ ➮ PAGE ▲ ▼ ▲ ▼ ▲ ▼ VIEW VIEW VIEW RESET RESET RESET DATA DATA DATA Chromalox 3101 Operator's Manual...
Security Every parameter or selection in the 3101 control- Levels ler’s setup PAGEs has an identifying MENU. Each MENU is assigned one of four Security Levels, A-D. In each level you may view certain MENUs, and adjust certain MENUs. This allows you to...
LOCK on the SET PAGE, adjustment of all parameters is locked out. An additional security number can be added using the menu for User Selectable Security Code (SET PAGE, menu CODE). Chromalox 3101 Operator's Manual...
Page 27
3. To reset the menus Time Over Setpoint timer (TOSP) and Peak Temperature Displays (PEAK), RESET press while the menus are displayed. 4. To exit the Display Page, press and hold RESET for 3 seconds. Chromalox 3101 Operator's Manual...
Digital Communications Throughout the following Setup PAGEs you will More fi nd these symbols . This indicates a section Info of this User’s Manual where more specifi c infor- mation on a parameter/application/feature can be found. Chromalox 3101 Operator's Manual...
Page 29
458-735 = Security level C 736-999 = Security level D Ambient Temperature Low -3 to 153 A LO Ambient Temperature High -3 to 153 A HI Lower Display Disable ON = Enabled LDSP OFF = Disabled Chromalox 3101 Operator's Manual...
Page 30
INLO Input high INHI DONE = Calibration fi nished Analog Output Zero 0 to 4095 AO 0 Calibration Analog Output Span 0 to 4095 AO S Factory Calibration Recovery Ready RECC Wait ---- DONE = Finished Chromalox 3101 Operator's Manual...
Page 31
Alarm 1 Low Setpoint Instrument Sensor Span ALO1 Alarm 1 High Setpoint Instrument Sensor Span AHI1 Output 1 Dead Band 0 to 100°F (Alarm Hysteresis) (.00 to 6.25% of span for analog inputs) Alarm 1 Inhibit INH1 Chromalox 3101 Operator's Manual...
Page 32
Alarm 2 Low Setpoint Instrument Sensor Span ALO2 Alarm 2 High Setpoint Instrument Sensor Span AHI2 Output 2 Dead Band 0 to 100°F (Alarm Hysteresis) (.00 to 6.25% of span for analog inputs) Alarm 2 Inhibit INH2 Chromalox 3101 Operator's Manual...
Section 5 Limit Control Operation Limit The 3101 High/Low Limit Controller provides con- Control trol output and visual indication when the process Operation variable exceeds the limit setpoint. The control- ler can be setup to operate as a high or low limit controller at the “controller type”...
Page 35
(see Figure 5.1 on the following page). Power Down Recovery: In the event of a power failure, the 3101 will re- tain the current status of the Limit Alarm, record the Time Over Setpoint (TOSP) and Peak Tem- perature value (PEAK).
Limit When the process variable exceeds the limit setpoint, the relay output is de-energized and the Limit LED comes ON. The Limit Alarm cannot be reset until the process variable falls below the Limit Setpoint Deadband. Chromalox 3101 Operator's Manual...
Page 37
Alarm Acknowledge Switch. The digital input function is setup on the SET PAGE, menu ENTI. See page 41 for details. Over The 3101 is equipped with a timer to register the Setpoint total process time over setpoint. This internal tim- Timer er begins recording the total time of the process over (or under) the limit setpoint.
Page 38
Peak The 3101 also records and displays the peak Temperature (minimum or maximum) temperature when the Display process variable exceeds the setpoint. VIEW DATA To see the PEAK temperature, press access the PEAK menu: DISP PEAK PEAK ➮ ➮ PAGE ▲...
Section 6 Alarms The 3101 controller has one alarm output (Alarm #1) and an optional Alarm #2 output. The optional Alarm #2 output is indicated by the following model numbers: Optional Outputs Model Number Alarm #2 3101 - 11*1* 3101 -...
Alarm Inhibit is selectable (ON/OFF) for each alarm output. INH2 ▲ ▼ RESET VIEW DATA Temperature Figure 6.1 Low Alarm Power Inhibit Normal Temperature Alarm Deadband Lo Alarm Setpoint Process Variable Lo Alarm Inhibit Lo Alarm Cleared Chromalox 3101 Operator's Manual...
Page 42
The alarm cannot be re- set until the process is out of the alarm condition. The Digital Input provides a remote alarm reset button (see page 41). ENTI RESET VIEW ▲ ▼ DATA Chromalox 3101 Operator's Manual...
Page 43
Alarm 1 Low Setpoint Instrument Sensor Span ALO1 Alarm 1 High Setpoint Instrument Sensor Span AHI1 Output 1 Dead Band 0 to 100°F (Alarm Hysteresis) (.00 to 6.25% of span for analog inputs) Alarm 1 Inhibit INH1 Chromalox 3101 Operator's Manual...
Page 44
Alarm 2 Low Setpoint Instrument Sensor Span ALO2 Alarm 2 High Setpoint Instrument Sensor Span AHI2 Output 2 Dead Band 0 to 100°F (Alarm Hysteresis) (.00 to 6.25% of span for analog inputs) Alarm 2 Inhibit INH2 Chromalox 3101 Operator's Manual...
Section 7 Digital Event Input The 3101 controller Digital Event Input allows you to use a pushbutton contact to function as a remote Alarm Reset. The external switching device is connected to the controller Digital Input at terminals 1 and 2 (see page 10 for wiring instructions).
The Analog Output Option is provided on control- Output lers with model number Option • 3101 - 111** This option can be used to transmit process variable to a remote recorder, computer or other device via a 4-20mA or 1-5Vdc signal, selectable by a switch on the bottom of the controller.
500°F = 20mA). SCAL PAGE VIEW ▲ ▼ RESET DATA Custom Scaling Page MENU Description Available Settings Security Analog Process Instrument Sensor Span AOTL Output - Low Analog Process Instrument Sensor Span AOTH Output - High Chromalox 3101 Operator's Manual...
User’s Manual provided with the software. Hardware Setup RS232 can be used to connect a computer or mo- dem to a single 3101 controller. RS232 lines can be run over distances up to 50 feet. RS422 and RS485 provide multidrop network...
Wiring connections for the digital communica- tions interface are made on terminals 9-13 using shielded serial interface cable. RS232 Communications 3101 Computer Figure 9.2 RS232 Wiring Connections Note: The DTR output is always enabled when the 3101 power is on. Chromalox 3101 Operator's Manual...
Instructions are also given for: • Factory Calibration Recovery • Calibration Offset When is The 3101 controller is factory calibrated before Calibration shipment to you, therefore, it is not necessary to Required? calibrate the controller when you receive and in- stall it.
Page 57
4. To access the calibration, you will need to be at LEVEL D security. Enter Security Code “736” at menu LOCH on the SET PAGE. Sensor The sensor input of the 3101 can be calibrated Input using an appropriate sensor simulator and the Calibration Sensor Calibration menu on the Input Page.
Page 59
2. Go to menu AO O. Adjust the value in the lower display—using —until the meter reads 4mA or 1.000 Vdc. AO O RESET VIEW ▲ ▼ DATA Chromalox 3101 Operator's Manual...
Page 60
The Factory Calibration Recovery should be used as a “starting point” for recalibration, should the unit become severely out of calibration. Factory Calibration Recovery is performed on the INPT PAGE, menu RECC. RECC ▲ ▼ RESET VIEW DATA Chromalox 3101 Operator's Manual...
Page 61
To establish the calibration offset: 1. Go to menu COFF on the Input Page. COFF ▲ ▼ VIEW RESET DATA 2. Use to set the calibration offset, adjustable from -100 to 100°F. COFF RESET VIEW ▲ ▼ DATA Chromalox 3101 Operator's Manual...
Process Variable Output Signal 4-20mA into 0-800 load 1-5 Vdc into 100K or greater load Selectable via DIP switch Range Programmable over selected sensor span for retransmission of Process Variable Accuracy ±0.2% of programmed span, ±1 LSD Chromalox 3101 Operator's Manual...
Page 63
Depth Behind Projection 4.00 inches (102 mm) Front Panel Projection 0.75 inches (19 mm) Panel Cutout 3.6 x 3.6 inches (92 mm x 92 mm) Case Material High Impact, Black ABS Plastic Front Panel NEMA 4X Construction Chromalox 3101 Operator's Manual...
Page 64
+3°F for 1000 Ft. of 18 AWG extension wire B Thermocouple +6°F for 1000 Ft. of 18 AWG extension wire T Thermocouple +1°F temperatures > -112°F (-80°C) +2°F temperatures < -112°F (-80°C) RTD, 4-20mA, 1-5 Vdc ±0.1% of Sensor Span/20 bbalanced leadwire resistance Chromalox 3101 Operator's Manual...
Troubleshooting The following Troubleshooting Guide gives simple solutions to common problems, and explains the 3101’s Error Messages. Should you have a prob- lem with your controller, it is a good idea to check this Guide for possible corrections before contact- ing the factory.
Chromalox are warranted only to the extent and in the man- ner that the same are warranted to Chromalox by Chromalox’s vendors, and then only to the extent that Chromalox is reasonably able to enforce such...
Page 69
Upon buyer’s submission of a claim as provided above and in its substantiation, Chromalox shall at its option either (i) repair or replace its Prod- ucts, parts or work at the original f.o.b. point of delivery or (ii) refund an equitable portion of the purchase price.
Digital Comm. Mode Selection P6/M1 Baud Rate P6/M2 Address P6/M3 * For digital communications using the Ascii Line Mode, you will use PAGE#/MENU# instead of the alphanumeric cues. For example, Alarm 1 Low Setpoint would be P4/M4. Chromalox 3101 Operator's Manual...
Page 71
Settings for: Limit Control Alarms Input Digital Communications Calibration Digital Input Analog Process Output Security Codes Security Security Adjust Security Codes Level Code Level - - - A, B A, B, C A, B, C, D Chromalox 3101 Operator's Manual...
Page 72
123-457 = Security level B 458-735 = Security level C 736-999 = Security level D Ambient Temp Low -3 to 153 Ambient Temp High -3 to 153 Lower Display ON = Enabled LDSP Enable OFF = Disabled Chromalox 3101 Operator's Manual...
Page 73
Input high INHI DONE = Calibration fi nished Analog Output Zero 0 to 4095 AO 0 Calibration Analog Output Span 0 to 4095 AO S 3902 Factory Calibration RDY Ready RECC Recovery Wait ---- DONE = Finished Chromalox 3101 Operator's Manual...
Page 74
Alarm 1 Low Setpoint Instrument Sensor Span Span Low ALO1 Alarm 1 High Setpoint Instrument Sensor Span Span High AHI1 Output 1 Dead Band 0 to 100°F 1°F (Alarm Hysteresis) (.00 to 6.25% of span for analog inputs) Alarm 1 Inhibit INH1 Chromalox 3101 Operator's Manual...
Page 75
Alarm 2 Low Setpoint Instrument Sensor Span Span Low ALO2 2 High Setpoint Instrument Sensor Span Span High AHI2 Output 2 Dead Band 0 to 100°F 1°F (Alarm Hysteresis) (.00 to 6.25% of span for analog inputs) Alarm 2 Inhibit INH2 Chromalox 3101 Operator's Manual...
Page 76
Digital Communications Page: DIG PAGE MENU Description Available Settings Factory Settings Security Mode = Disabled DIGT CPIF Selection CPIF = Computer Interface LINE = ASCII Line Baud Rate 1200 BAUD 19.2K 2400 4800 9600 19.2K Address 1 to 255 ADDR Chromalox 3101 Operator's Manual...