Mitsubishi Electric CITY MULTI PEFY-P80VMH-E-F Technical & Service Manual page 8

Multiple split type air-conditioners
Table of Contents

Advertisement

3-2. Electrical parts specifications
Model
Symbol
Parts
name
Tranrsformer
T
Liquid pipe
TH22
thermistor
Gas pipe
TH23
thermistor
Outdoor air
temperature
TH24
thermistor
Fuse
FUSE
(Indoor con-
troller board)
Fan motor
(with Inner-
MF1,2
thermostat)
Inner-
thermostat
(Fan motor)
Fan motor
C1
capacitor
Linear
LEV
expansion valve
Power supply
TB2
terminal block
Transmission
TB5
terminal block
TB15
7
PEFY-P80VMH-E-F
(Primary) 50/60Hz 220-240V (Secondry) (23.5V 0.9A)
Resistance 0˚C/15kΩ,10˚C/9.6kΩ,20˚C/6.3kΩ,25˚C/5.4kΩ,30˚C/4.3kΩ,40˚C/3.0kΩ
Resistance 0˚C/15kΩ,10˚C/9.6kΩ,20˚C/6.3kΩ,25˚C/5.4kΩ,30˚C/4.3kΩ,40˚C/3.0kΩ
Resistance 0˚C/15kΩ,10˚C/9.6kΩ,20˚C/6.3kΩ,25˚C/5.4kΩ,30˚C/4.3kΩ,40˚C/3.0kΩ
4-pole OUTPUT 90W
NS-80VMHF
4.0µF✕440V
DC12V Stepping motor drive
port dimension ø 5.2
0~1800pulse
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>
(L,N,
) 330V 30A
PEFY-P140VMH-E-F
250V 6.3A
4-pole OUTPUT 130W
NS-100VMHF
OFF 135˚C±5˚C
ON 95˚C±20˚C
DC12V Stepping motor drive
port dimension ø 6.4
0~1800pulse
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>
(1,2),(M1,M2,S) 300V 10A
PEFY-P200VMH-E-F
4-pole OUTPUT 200W
NS-200VMH-E-F
-
DC12V Stepping motor drive
port dimension ø 5.2
0~1800pulse
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>
(L1,L2,L3,N,
PEFY-P250VMH-E-F
4-pole OUTPUT 230W
NS-250VMH-E-F
) 660V 40A