Trouble Shooting - Mitsubishi Electric CITY MULTI PEFY-P80VMH-E-F Technical & Service Manual

Multiple split type air-conditioners
Table of Contents

Advertisement

7

TROUBLE SHOOTING

7-1. How to check the parts
Parts name
Liquid pipe thermistor
Disconnect the connector, then measure the resistance using a tester.
(TH22)
(Sorrounding temperature 10°C~30°C)
Gas pipe thermistor
(TH23)
Outdoor air temperature
thermistor
(TH24)
Trans
Disconnect the connector and measure the resistance using a tester.
CN3T
CNT
3T
3
1
·
PEFY-P80
Fan motor
Relay connector
Protector
Fan motor
PEFY-P200
Protector
Linear expansion
Disconnect the connector then measure the resistance valve using a tester.
valve
CN60
White
1
Yellow
2
Orange
3
LEV
Blue
4
Red
5
Brown
6
Drain Pump
Disconnect the connector then measure the resistance
(Drain water lift up kit)
valve using a tester.
(Sorrounding temperature 20°C~30°C)
Red
1
Red
3
Drain sensor
Measure the resistance between the terminals using
(Drain water lift up kit)
a tester.
3
1
13
Normal
4.3k
~9.6k
Open or short
Normal
CNT(1)-(3)
App.15
CN3T(1)-(3)
App.4
140
Measure the resistance between the terminals using a tester. (at 20˚C)
Motor terminal
or
Relay connector
Gray
1
2
Gray-Orange
3
Black
4
Gray-Black
Orange
5
Brown
6
Gray-Brown
7
Red
8
Gray-Red
Red
9
·
250
Measure the resistance between the terminals using a tester. (at 20˚C)
Relay connector
Motor terminal
Brown
or
4
Relay connector
Red-White
Red
1
Orange
8
White-Black
Orange
9
Red-Black
White
2
Brown-Gray
Gray
5
Black
3
Gray-Yellow
Yellow
6
Brown-Yellow
Normal
(1)-(5)
(2)-(6)
White-Red
Yellow-Brown
150Ω
Normal
399Ω
Open or short
(Refer to the thermistor characteristic graph)
0˚C/6.0kΩ, 10˚C/3.9kΩ
20˚C/2.6kΩ, 25˚C/2.2kΩ
30˚C/1.8kΩ, 40˚C/1.3kΩ
Check points
Abnormal
(Refer to the thermistor characteristic graph)
Abnormal
Open or short
Normal
PEFY-P80
PEFY-P140
76.4Ω
89.8Ω
115.2Ω
148.1Ω
Normal
PEFY-P200 PEFY-P250
4.17Ω
4.17Ω
4.17Ω
11.14Ω
12.44Ω
11.14Ω
12.44Ω
11.14Ω
12.44Ω
(3)-(5)
(4)-(6)
Orange-Red
Blue-Brown
±10%
Abnormal
Abnormal
22.8Ω
27.4Ω
Open or short
32.8Ω
67.9Ω
Abnormal
4.17Ω
4.17Ω
4.17Ω
Open or short
Abnormal
Open or short
<Thermistor characteristic graph>
Room temperature thermistor(TH21)
Liquid pipe thermistor(TH22)
Gas pipe temperature thermistor(TH23)
Drain sensor(DS)
=15kΩ ± 3%
Thermistor R
0
Fixed number of B=3480kΩ ± 2%
1
Rt=15exp { 3480(
273+t
0˚C
15kΩ
50
10˚C 9.6kΩ
20˚C 6.3kΩ
40
25˚C 5.2kΩ
30˚C 4.3kΩ
40˚C 3.0kΩ
30
20
10
0
-20 -10 0 10 20 30 40 50
1
) }
273
Temperature (˚C)

Advertisement

Table of Contents
loading

Table of Contents