Setting of volume and signal tone

To set volume and signal tones the cover of the housing has to be removed. The electrical plug connection to the bottom
section can be cut. In the upper section the setting can be carried out at the 12 slide switches. The sounder dEV20
disposes of two signal levels. The signal tone for the first level is adjusted with the slide switches 1-5 (S0) according to
the signal choice list. The signal tone for the second signal level is adjusted with the slide switches 6-10 (S1).
The volume is set by the slide switches 11 and 12 (see table).
The shift from the first to the second signal level in case of devices direct tension is realized by additional application of
a positive operation voltage on clamp 3. In case of alternating tension the shift is made by additional application of the
phase (L1) of the operation voltage on clamp 3.
After the completion of the setting the electrical connection to the bottom section has to be re-established and the upper
section has to be fixed with the respective screws on the bottom section. (CAUTION! Don't damage the gap of the
joint.) The locking torque of the screws is: 1.2 ... 1.5 Nm

ISO 9001

The information regarding scope of delivery, application, operation and operation conditions is current as of publication
date and subject to change.

Recycling

The complete disposal of the device is made together with e-waste. When disassembling the device the components
polyester, metal and electronics have to be disposed separately. In any case please be aware of the disposal conditions
of the specific country.

Safety instructions

Please read this manual and observe the country-specific assembly standards as well as the valid safety instructions and
accident prevention regulations. Intervention at the device beyond the connection handling is the exclusive business of
the manufacturer. Reconstructions or changes of the product are not allowed. The device shall only be used in a safe and
proper condition. The electrical connection in the housing shall only be made byskilled personnel.

Attention ex-area

To comply with the temperature range indicated on the name plate of the device, the ambient temperature, terminal
cross-section as well as the selfheating of the operating material has to be observed.
The responsibility regarding the intended use of the sounder, with reference to the existent general framework in these
instructions shall be exclusively incumbent on the operating company.

Care and maintenance

The requirements of EN 60079-17 regarding the regular control of the explosion protection must be applied. The
signalling light contains no serviceable parts.

Technical Specifications

Ambient condition
Ambient temperature according to temperature class T6
Housing degree of protection
Protection class
Warning
Acoustic specification
Volume
Signal tone
Delivery condition
Electric specification
Power consumption
AC
Overvoltage category
DC
Connecting Terminal
Rated cross-section
Multi-conductor connection
Tightening torque for clamp screw
-50°C ≤ Ta ≤ +60°C
IP66
I
Holding time before opening: 10 Min. in case of 230 VAC / 2 Min. in case of 24 VDC
1
max. 115 dB(A) reducible in 3 levels each by 10 dB
32 for each signal level
S0: Tone 24 / S1: Tone 4
max. 14 W
Ue = 85 VAC ... 264 VAC
II
Ue = 24 VDC ±20% 19,2 VDC ... 28,8 VDC
up to 2.5 mm
(AWG 14)
2
max. 2 x 1 mm
2
0.4 Nm
DEV20 SOUNDER TECHNICAL MANUAL
DEV20 Sounder Technical Manual
TMF0047.A
www.eaton.com