Chapter 3 Quick Start; Setting Steps For Installation - Delta DeviceNet CME-DN01 User Manual

Table of Contents

Advertisement

3.1 Setting Steps for Installation

Step 1. Setting communication format of the AC drives to 19200 RTU 8, N, 2.
Step 2. Setting frequency source of the AC drives to operate from RS-485.
Step 3. Setting operation source of the AC drives to operate from communication interface.
Note: Refer to the following table for setting step 1, step 2 and step 3.
VFD-E
P02-00=3
P02-01=3
P09-01=2
P09-04=3
Step 4. Using RJ11 (6 pins) to connect RS-485 of the CME-DN01 and the AC drive.
Step 5. Adding the EDS files (generated from the auto EDS generator software, can be
downloaded from Delta website http://www.delta.com.tw/industrialautomation/) into DeviceNet
management software.
Step 6. Using the operation method of DeviceNet management software for CME-DN01
connection.
Note: Please make sure that VFD-E has set as above table. Or CME-DN01 cannot work
correctly. SP LED should be Green after finishing Step 4 and indicates the CME-DN01 is
communicating with the AC motor drive. If the SP LED is not ON, please refer to chapter 4
Troubleshooting to solve the problem.
Revision September 2017, 2006PDD23000003
Description
Master frequency determined by RS-485
Operating instructions determined by the RS-485
19200 bits/second
Modbus RTU mode, 8 bits, no parity and 2 stop bits

Chapter 3 Quick Start