Dual tech detector switch

Advertisement

Dual Tech detector switch
7. SETTINGS
- Parameters:
Sensor parameters
Default
value
Time delay
15 mn
PIR (ultra high)
Sensitivity
/ US (high)
Brightness threshold
500 lux
Auto on/Auto off
Inactive
Passage mode
Active
Manual on/Auto off
Inactive
Initial
PIR and US PIR and/or US, PIR, US,
Hold
PIR or US
Reactivation
PIR or US
Alert
Inactive
Calibration
Regulation
Active
Light input
Auto
Time delay: Time for which light is switched on following detection.
Sensitivity: Detector range setting.
Brightness threshold: Brightness value below which the light is switched on
and above which the light is switched off.
Auto on/Auto off mode:
The light is switched on automatically:
- When presence is detected, if the natural brightness is too low.
The light is switched off automatically:
- Where no presence is detected and at the end of the time delay set.
- Or if there is a sufficient level of natural light (activated setting).
Any new detection causes an automatic switch on if there is insufficient light.
Passage mode:
- If there is no presence detected in the 3 minutes following an initial detection,
the product will cut off after 3 minutes.
- If a new presence is detected in the 3 minutes following the initial detection,
the device will cut off at the end of the time delay set.
Manual on/Auto off mode:
Comes on via a manual switch, automatic switch off:
- Where no presence is detected and at the end of the time delay set.
Following switch off, any new detection within a 30-second period will cause the
device to be switched on automatically.
After 30 seconds the device is switched on via a manual switch.
Initial detection: Light switched on from first detection.
Hold: The load remains active if any new presence is detected.
Reactivation: Function allowing automatic start of the product at the end of
30 seconds following the load being switched off.
Upon being switched off, any new detection within a 30-second period will cause
the device to be switched on automatically.
After 30 seconds the device must be switched on manually.
Calibration: The surrounding level of light measured with a luxmeter will then
have to be transmitted to the detector.
Regulation: Light switched off automatically 10 minutes after the brightness
threshold has been exceeded. If the light level is below the brightness threshold,
the light is activated automatically after 20 seconds.
Light input: Quantity of additional lux provided when the light is switched on.
Technical data sheet: F01013EN/01
CONTENTS
Modifiable parameters
Configuration
tools
88230 88235
3,5,10,15,20 min
0 - 59 min 59s
Low, medium, high, ultra high
20, 100, 300, 500, 1000 lux
0 - 1275 lux
Activatable/Deactivatable
Activatable/Deactivatable
Activatable/Deactivatable
PIR and/or US, PIR, US,
PIR and/or US, PIR, US,
Deactivatable
Activatable/Deactivatable
0 - 99995 lux
Activatable/Deactivatable
Auto - 1275 lux
Updated: 31/05/2010
Cat. No(s): 488 06
7. SETTINGS (cont.)
- Modifying parameters using configuration tools
• 882 35: Simplified configuration tool
• 882 30: Advanced configuration tool
When the detector receives an IR command from a configuration tool
it emits a beep acknowledging the modification.
- Return to factory settings:
First press: Press LEARN briefly, the LED blinks slowly.
Second press: Keep LEARN pressed down for 10 seconds until the
LED blinks rapidly.