Mounting requirements
This instrument is intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
The instrument can be mounted on panel (thickness 12 or 29 mm max.). When the maximum front protection (IP65) is desired, the optional screw type bracket (#2) must be mounted.
R38: 100/240 Vac model
R38: 24 Vac/dc - 12 Vdc models
External resistance: 100W max., error 0.5% of span max..
Cold junction: Automatic compensation from 0 to 50°C.
Cold junction accuracy: 0.1°C/°C after a warm-up of 20 minutes.
Input impedance: > 1 MW.
Calibration: According to EN 60584-1.
Note: Por TC wiring use proper compensating cable preferable shielded.
Input circuit: Current injection (135 µA).
Line resistance: Not compensated.
Calibration: According to EN 60751/A2.
Input circuit: Current injection (25µA).
Line resistance: Not compensated.
Outputs Safety notes
Relay
Contact rating: 8 A /250 V cosj =1; 3 A /250 V cosj =0.4;
Operations: 1 x 10 5.
SSR
Logic level 0: Vout < 0.5 Vdc;
Logic level 1: 12 V ±20% @ 1 mA; 10 V ±20% @ 20 mA.
Relay
Contact rating: 8 A /250 V cosj = 1; 3 A /250 V cosj = 0.4;
Operations: 1 x 10 5.
SSR
Logic level 0: Vout < 0.5 Vdc;
Logic level 1: 12 V ±20% @ 1 mA; 10 V ±20% @ 20 mA.
100 ÷ 240 Vac
Power consumption: 3.6 VA max.
Supply voltage: 100 ÷ 240 VAC/DC (+10%)
12 Vdc - 24 Vac/dc
Power consumption: 1.44 W (12 V), 3.15VA (24 V) max.;
Supply voltage: 12 VDC (-15 ÷ +10%) 24 VAC/DC (-15 ÷ +10%)
Notes:
Technical specifications
Case: Plastic, self-extinguishing degree: V-0 according to UL 94.
Front protection: IP 65 (when the screw type bracket is mounted) for indoor locations according to EN 60070-1.
Rear terminals protection: IP 20 according to EN 60070-1.
Installation: Panel mounting.
Terminal block: 11 screw terminals (screw M3, for cables of 0.25 ÷ 2.5 mm2 or from 22 AWG to 14 AWG).
Dimensions: 75 x 33 mm, depth 75.5 mm.
Cutout: 71 (-0 ÷ +0.5 mm) x 29 (-0 ÷ +0.5 mm).
Weight: 180 g approximately.
Insulation voltage: 2300 V rms according to EN 61010-1.
Display: One 3 digits red display h 12 mm.
Display updating time: 500 ms.
Sampling time: 130 ms.
Resolution: 20000 counts.
Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room temperature.
Electromagnetic compatbility and safety requirements:
Compliance: EMC directive 2004/108/CE (EN 61326-1),
LV directive 2006/95/CE (EN 61010-1).
Installation category: II.
Pollution category: 2.
Temperature drift: Is part of the global accuracy.
Operating temperature: 0 ÷ 50°C (32 ÷ 122°F).
Storage temperature: -30 ÷ +70°C (-22 ÷ 158°F).
Humidity: 20 ÷ 85% RH, non condensing.
Note: The screw type bracket # 2 (necessary to obtain the IP65 front protection) and other options can be requested to our sales offices.
When the instrument is powered, it initially works according to the parameter values loaded in its memory.
The instruments behavior and its performance are governed by the value of the memorized parameters.
At the first start up the instrument will use a "default" parameter set (factory parameter set); this set is a generic one (e.g. a TC J input is programmed).
We recommend that you modify the parameters to suit your application (e.g. set the right input type, Control strategy and define an alarm, etc.).
To change these parameters you will need to enter the "Configuration procedure".
At power up the instrument can start in one of the following modes depending on its configuration:
Auto mode
Stand by mode (St.bY)
We define the above conditions as "Standard Display".
Press key and keep it pressed.
Condition 1:
The instrument shows (lock ON). The keyboard is locked.
Mantaining the pressure on the key, also press the
key.
The LED Set begins to flash.
Keep the pressure on the two keys until the display shows (lock OFF).
Now release the keys. The keyboard is now unlocked.
Note: If no button is pressed for a time longer than the time programmed with the Lo parameter, the key lock will be automatically enabled.
Condition 2:
The instrument displays no message. In this situation we can have 2 different cases:
Case 1: The parameters protection (password) is not active.
Press key and keep it pressed for around 5 seconds.
The display shows the code of the first configuration parameter.
With the /
keys, select the parameter to be edited.
Case 2: The parameters protection (password) is active.
Press key and keep it pressed for more than 5 seconds.
The display shows the code that identifies the first parameter that has been moved into the Operator level.
Press key. The display shows
.
Press key again. The display shows
.
With the /
keys, program the password and confirm it pushing
key again.
Note: The factory default password is 0 (no password).
2.A) If the password is correct, the instrument shows the code that identifies the first configuration parameter.
2.B) If the password is not correct, the instrument shows again.
Note: The instrument shows the parameters applicable to the hardware options in accordance with the specific instrument configuration [i.e. setting "AL1t - Alarm 1 type" equal to nonE (not used), all parameters related with the alarm 1 will be skipped].
To exit from the programming mode do not touch any key for around 30 s, or press key for around 5 s.
The instrument has a function that protects the parameters through a password, programmable through parameter . If you wish to have this protection, you must set the
parameter to the number you would like to be your password and then exit from parameters programming.
When the protection is active, to be able to have access to the parameters, press the key and keep it pressed for about 5 s. Afterwards, the display shows
, press
again, the instrument shows
.
Now, through the and
keys, set the number of your password and press
again.
If the password is correct the display shows the code that identifies the first parameter and it will be possible to program it with the same procedure as described on the previous paragraph.
The password protection is disabled when =
.
If the password is forgotten, use password -
.
This allows to access the protected parameters and verify/ modify the parameter.
(levels of parameters programming)
The factory programming hides all the parameters behind the password with exception of the set point 1.
If you wish to modify some parameters, maintaining the protection on the others, after setting the Password through parameter, follow this procedure:
a) Enter the programming through the Password.
b) Select the parameter to be programmable without Password.
c.1) The Set LED is flashing.
The parameter is protected by the password.
c.2) The Set LED is lit but not flashing.
The parameter is not protected by the password.
To modify the level of access of the parameter (in other words: to have the parameter protected or not by the password) press the key and keeping it pressed press the
key.
The Set LED will change its state, pointing out the new level of accessibility of the parameter (switched on = not protected; flashing = protected by password).
If the Password is enabled and some parameters have been set as "not protected", entering the programming mode the instrument will first display all the parameters set as "not protected" and then the parameter. By entering the password here all other parameters can be viewed.
It is possible to restore the instruments factory configuration. To load the factory default parameter settings, proceed as follows:
Once the password has been confirmed by pressing the key, the display shows for approximatively 2 s "---", the instruments then runs through the start up procedure resetting all the parameters to the factory defaults.
When supplied, the instrument can assume 2 different conditions:
ON: Means that the controller activates the programmed control functions.
STAND-BY: Means that the controller activates no control functions and the control outputs are forced to zero (the display results switched ON or OFF according to the parameter setting).
The controller starts in the same way it was before the switch OFF.
The ON/STAND-BY condition can be selected pressing the key for 1 s.
The passage from STAND-BY to ON condition, does not activate the Soft-start (or ) or the Autotuning and hides the alarms. When the instrument is in STAND-BY mode with the display on the display alternates between the measure value and
.
When the instrument is in STAND-BY with display OFF, the display is completely dark except for the decimal point of the LSD [Set LED (5)].
When the instrument is in STAND-BY mode (display ON or OFF) it is however possible to enter the parameters programming.
In the following pages we describe all the instrument parameters. However, the controller shows the parameters applicable to the hardware options in accordance with the specific instrument configuration [i.e. setting "o2F - Alarm 2 function" equal to (not used), all parameters related with that alarm will be skipped].
[1] SPL - Minimum Set Point value
Range: From -99.9 to SPH engineering units.
[2] SPH - Maximum Set Point value
Range: From SPL to 999 engineering units.
[3] SP1 - Set Point
Range: From SPL to SPH engineering units.
[4] SP2 - Second Set Point
When 2 control outputs are programmed with ON/OFF action, the instrument uses SP1 to command OUT1 and SP2 (see following parameter) to command OUT2.
Available: When Out2 has been programmed as control output.
Range: From SPL to SPH engineering units.
[5] AL - Alarm threshold
Available: When Out2 has been programmed as alarm.
Range: -99.9 ÷ 999 engineering units.
[6] tun - Autotuning
Available: When o1.F = PID
Range:
Note: When the Autotuning and the soft start, or the delay at the start up, have been programmed, the instrument performs first the soft start (with the parameters it has in memory) and then performs the Autotuning.
[7] Pb - Proportional band
Available: When o1F = PID and tun = ub.
Range: 1 ÷ 999 engineering units.
[8] ti - Integral time
Available: When o1F = PID and tun = ub.
Range: OFF (excluded)/1 ÷ 500 seconds.
[9] td - Derivative time
Available: When o1F = PID and tun = ub.
Range: OFF (excluded)/1 ÷ 200 seconds.
[10] SEn - Input type
Model | Selection | Sensor | Measuring range |
F | J.C | TC J | -40 ÷ 999°C |
Ca. C | TC K | -40 ÷ 999°C | |
J.F | TC J | -40 ÷ 999°F | |
Ca. F | TC K | -40 ÷ 999°F | |
A | Pt. C | PT 100 | -50.0 ÷ 850°C (autoranging) |
Pt. F | PT 100 | -58.0 ÷ 999°F (autoranging) | |
T | nC.C | NTC | -50.0 ÷ 109°C (autoranging) |
PC.C | PTC | -50.0 ÷ 150°C (autoranging) | |
nC.F | NTC | -58.0 ÷ 228°F (autoranging) | |
PC.F | PTC | -58.0 ÷ 302°F (autoranging) | |
P1.C | Pt 1000 | -50.0 ÷ 850°C (autoranging) | |
P1.F | Pt 1000 | -58.0 ÷ 999°F (autoranging) |
[11] dP - Decimal point
Range:
[12] CA - Offset on the displayed value
Range: -300 ÷ 300 engineering units.
[13] Ft - Filter on the displayed value
Range: 0 (excluded)/1 ÷ 20 seconds.
[14] o1F - Out1 function
Range:
[15] tr1 - Out1 cycle time
Range: 1 ÷ 250 seconds.
[16] o2F - Out2 function
Range:
Note: The Neutral Zone functioning is used to control the plants with an element that causes a positive increase (ex. Heating, Humidifying etc.) and an element that causes a negative increase (ex. Cooling, Dehumidifying etc.).
The control works on the programmed outputs depending on the measure, on the active Set point "SP", and on the programmed hysteresis "d1".
The controller works in the following way: it switches OFF the outputs when the process value reaches the Set Point and activates the heating output when the process value is lower than [SP - d1], or it switches on the cooling output when the process value is higher than [SP + d1].
Accordingly, the element that causes the positive increase must be connected to the output programmed as heating, while the element of negative increase must be connected to the output programmed as cooling.
O1F | O2F | Displayed parameters |
H.rE | H.AL, L.AL, b. AL, dHA, dLA | SP1, AL |
C.rE | H.AL, L.AL, b. AL, dHA, dLA | SP1, AL |
on. H | H.AL, L.AL, b. AL, dHA, dLA | SP1, AL |
SP.C, SP.H | SP1, SP2 | |
Nr | SP1 only | |
on. C | H.AL, L.AL, b. AL, dHA, dLA | SP1, AL |
SP.C, SP.H | SP1, SP2 | |
Nr | SP1 only |
[17] d1 - Out1 hysteresis or neutral zoneAvailable: When Out1 is equal to hn. H or on. C.
Range: 0.1 ÷ 999 engineering units.
[18] d2 - Out2 hysteresis
Available: When o2F is different from nr.
Range: 0.1 ÷ 999 engineering units.
[19] AL.F - Alarm function
Available: When o2F is programmed as alarm output.
Range:
AL = Automatic reset Alarm
AL.n = Latched Alarm
AL.a = Acknowledged Alarm
[20] AL.t - Inhibition time of the alarm at start up or after a Set Point change
Range: 0 = OFF (any hidding)/0.01 ÷ 9.59 hh.mm.
Note: When the measure reaches the alarm threshold, the instrument disables the hidding of the alarm.
[21] Pct - Compressor protection time
The protection prevents the output cycling and therefore reduces relay wear by waiting for the time setting to elapse before allowing a subsequent switching of the output. In other words, it defines the minimum time that will pass between the switch off of a cooling output and its following reactivation.
Available: When at least one output is programmed ascooling output.
Range: 0 (OFF)/0.01 ÷ 9.59 hh.mm.
Note: This parameter has effect to ALL the cooling outputs.
[22] SSt - Soft start time
Range: 0 (OFF)/0.01 ÷ 9.59 hh.mm.
Note: When the control type is ON/OFF, the time of the soft start becomes an output time delay, the power is forced to 0 and the parameter SSP is hidden.
[23] SSP - Power during Soft Start
Available: When Sst is different from 0.
Range: 0 ÷ 100%.
Note: If programmed = 0, also the alarms and/or the second control output remains = 0 and the instrument displays
for the programmed time.
[24] ub. F - key function
Range:
[25] PP - Parameters protection Password
Range: 1 ÷ 999.
[26] Lo - Time for the Key lock automatic enable
This parameter allows to set the time that the instrument will wait before to automatically enable the key lock. The time count will re-start after a key pressure.
Range: 0 (lock disabled)/1 ÷ 30 minutes.
The display shows the OVER-RANGE and UNDERRANGE conditions with the following indications:
Over range
Under range
The sensor break will be signaled as follows:
Sensor break
Note: When an over-range or an under-range is detected, the alarms operate as in presence of the maximum or the minimum measurable value respectively.
To check the out of span Error condition, proceed as follows:
AtE- Auto-tune not finished within 12 hours.
EPr- Possible problem of the instrument memory.
The messages disappear automatically.
When the error continues, send the instrument to your supplier.
Every possible use not described in this manual must be considered as a improper use.
This instrument is in compliance with EN 61010-1 "Safety requirements for electrical equipment for measurement, control and laboratory use"; for this reason it must not be used as a safety equipment.
Ascon Tecnologic S.r.l. and its legal representatives do not assume any responsibility for any damage to people, things or animals deriving from violation, wrong or improper use or in any case not in compliance with the instrument's features.
Whenever a failure or a malfunction of the control device may cause dangerous situations for persons, thing or animals, please remember that the plant has to be equipped with additional safety devices.
We warrant that the products will be free from defects in material and workmanship for 18 months from the date of delivery. Products and components that are subject to wear due to conditions of use, service life, and misuse are not covered by this warranty. The warranty is limited to repairs or to the replacement of the instrument.
The tampering of the instrument or an improper use of the product will bring about the immediate withdrawal of the warranty's effects.
In the event of a faulty instrument, either within the period of warranty or further to its expiry, please contact our sales department to obtain authorisation for sending the instrument to our company.
The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found, without any fees or charge for Ascon Tecnologic, except in the event of alternative agreements.
Before supplying tension to the instrument, make sure that it is perfectly dry.
The appliance (or the product) must be disposed of separately in compliance with the local standards in force on waste disposal.
ASCON TECNOLOGIC S.r.l.
Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY
TEL.: +39 0381 69871 - FAX: +39 0381 698730
http:\\www.ascontecnologic.com
e-mail: info@ascontecnologic.com
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download ASCON TECNOLOGIC R38 - Microprocessor Based Digital Electronic Controller Quick Guide
Advertisement
Need help?
Do you have a question about the R38 and is the answer not in the manual?
Questions and answers