View motherboard

WARNING
Class 2 supply, 24 V shall be used.
DIP-switch S1
28 - 14 AWG
max. 4.5 lb-in
S1
Group 1
WARNING
For continued protection against fire,
replace only with the
same type and rating of fuse.
www.dh-partner.com
Power
115 VAC
mains connector
22 - 12 AWG
max. 6 lb-in
Encoding of group – DIP switches S1 - S5
Following functions can be adjusted for each group separately with DIP switches S1 - S5 on
motherboard of control panel and on group plug-in unit, if available.
The delivery state of all DIP-switches is OFF.
1 = ON
Drives CLOSE up to final position by single pressing on respective vent button.
1 = OFF
Drives are closing only so long as the vent button is pressed.
2 = ON
Drives OPEN up to final position by single pressing on vent button.
2 = OFF
Drives are opening only so long as the vent button is pressed.
3 = ON
Drives are automatically closed by trigger of function „Central CLOSE",
e.g. by rain detector or room temperature control.
3 = OFF
Drives can be closed only by pressing the respective vent button.
4 = ON
Drives are automatically opened by trigger of function „Central OPEN",
e.g. by room temperature control.
4 = OFF
Drives can be opened only by pressing the respective vent button.
4/12
GVL 8408-M-UL
For continued protection against fire, replace only with the same type
and rating of fuse or equivalent, adjacent to the fuse holders.
group 1-5: 22 - 12 AWG /
DIP-switch S2
fuse drive
fuse drive
group 1
group 2
S2
F3.15A
F3.15A
Group 2
Ventilation control panel
GVL 8408-M-UL
T2.5A
fuse mains
max. 4.5 lb-in
DIP-switch S3
DIP-switch S4
fuse drive
group 3
S3
S4
F3.15A
F3.15A
Group 3
Group 4
LED Power ON
English
DIP-switch S5
fuse drive
fuse drive
group 4
group 5
S5
F3.15A
Group 5
99.828.04 1.0/06/19