DMX
14. Possible connections for draw-out version
Installation of Terminal Adaptor available as an accessory.
Termination
support must
be made
of isolating
material and
sized according
to the bars in
order to avoid
performances
during
short circuit
conditions.
3
16 Nm
X
X
Icc (kA)
≤ 42
"X" max (mm)
350
≤ 50
300
93