Daikin RZVF50 Installation Manual page 42

For outdoor unit, new refrigerant r32
Table of Contents

Advertisement

Support bracket
1 -1.5 m
Downward slope of at least 1/100
Fig. 10
-&
If drain stagnates in the drain piping, the piping may be
CAUTION----------­
clogged.
• If sufficient downward inclination cannot be ensured,
carry out upward drain piping.
• Install supports at a distance of 1 to 1.5 m so that the
piping may not
• Make sure to use the attached drain hose (2) and the
deflect(Refer Fig. 10)
metal clamp (1).
Insert the drain hose (2) into the drain socket up to the
point where the socket diameter becomes larger. Put
the metal clamp (1) to the taped hose end .Be sure to
fasten the screw of the metal clamp (1 )until the margin
of the screw thread decreases to 4 mm or less.
Metal clamp (1)
Tape
Fig. 11
-&
• Tighten the metal clamp (1) on specified above otherwise.
CAUTION-----------
The drain hose (2), the socket or the metal clamp (1) may
be damaged.
• Wrap the vinyl tape around the end of the metal clamp
(1) so that the sealing material (Large) (5) to be used at
the next process may not be damaged with the clamp
end or bend the tip of the metal clamp (1) inward as
shown.
(Refer to Fig. 12)
Drain hose (2)
(accessory)
42
<In case of sticking vinyl tape>
"-
l
Tightened part
<In case of bending the tip>
Bend the tip without tearing the
sealing material (Large) (5).
Fig.12
< Caution to be taken when carrying out upward drain
• The maximum height of the drain riser is 467 mm. Since
piping (Refer to Fig. 13) >
the drain pump mounted on this indoor unit is a high
head type, from the characteristic point of view, the
higher the drain riser the lower the draining noise.
Therefore, the drain riser of 300 mm or higher is
recommended.
• For upward drain piping, keep the horizontal piping
distance of 300 mm or less between the drain socket
root to the drain riser.
Ceiling slab
300 or less
/
Metal clamp (1)
(accessory)
Drain hose (2)
(accessory)
Keep the drain hose level or make a slight up-grade so
that air may not stagnate in the drain hose.
If air stagnates, the drain may flow oppositely when
the drain p
p
tops and gen
:
\_
1
Fig.13
Vinyl tape
Stick vinyl tape without
tearing the sealing
material(
r
)(
5
_
_
__
(unit [mm])
0
Ad"ustable
(467 or less) t:::,
g
Upward drain piping
(Field supply)
Drain hose (2)
j
ra
abnormal s
n
: