Installation Of Indoor Unit - Daikin RZVF50 Installation Manual

For outdoor unit, new refrigerant r32
Table of Contents

Advertisement

(4) Open installation holes
(in the case of installation onto the existing ceiling).
• Open the installation holes on the ceiling of the
installation location, and work on the refrigerant piping,
drain piping, remote controller wiring (unless a wireless
remote controller is used), and wiring between the indoor
and outdoor units to the piping connection port and
wiring connection port of the indoor unit (refer to each
piping and wiring procedure items).
• Ceiling framework reinforcement may be required in
order to keep the ceiling horizontal and prevent ceiling
vibration after opening the ceiling holes. For details,
consult your building and upholstery work contractors.
(5) Install the hanging bolts.
• Use M10 bolts for hanging the indoor unit.
Use hole-in-anchors for the existing bolts and embedded
inserts or foundation bolts for new bolts, and fix the
indoor unit firmly to the building so that it may withstand
the mass of the unit.
In addition, adjust clearance (50 -100 mm) from the
ceiling in advance.
<Installation examples>
Note) Components shown in the figure above are
all local procurement.
Fig.3
-&
CAUTION------------
• Secure a sufficient maintenance space for the drain pan
and electrical components before installing the indoor
unit.
• Secure a sufficient maintenance space for the filter
chamber, and peripheral components before installing the
indoor unit.
them before installing the indoor unit. Refer to also the
installation manual attached to the optional parts.
specified parts.
Long nut or
turnbuckle
Hanging bolt
39

5. INSTALLATION OF INDOOR UNIT

Depending on the optional parts, it may be easier to attach
For installation, use the attached installation parts and
(1) Install the indoor unit temporarily.
• Connect the hanging brackets to the hanging bolts. Be
sure to the use and tighten the nut and washer( procured
in the field) for each hanging bracket from both upper and
lower sides of the hanging bracket. (Refer to the fig. 4) At
that time, the fall of the washer for the hanging bracket
can be prevented if the washing fixing plate (8) is used.
[Fixing hanging brackets]
Part to be procured in the field
Washer (Procured in the field)
I
Tighten from above and below
(Double nut)
[Fixing method of washers]
Washer fixing plate (8)
(accessory)
Fig.4
• Keep the air outlet covered with a protective sheet to prevent
weld spatter and other foreign materials from entering the
indoor unit and damaging the resin drain pan.
(If holes or cracks are generated in the resin drain pan, water
can leak.)
(2)
Adjust so that the unit is properly positioned.
(3)
Check the level of the unit.
(4) Remove the washer fixing plate used for preventing the
washer for hanger from dropping and tighten the upper
side nut.
Feed water into the tube and
set the indoor unit to the water
levels on the left and right.
[M aintaining horizontality]
Fig.5
Nut on the upper side
(Refer to Fig. 5)
Hanging bracket
Bottom of product

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents