CO2 Meter TON-0007 User Manual

CO2 Meter TON-0007 User Manual

Tongdy co2 monitor with relay

Advertisement

Tongdy CO2 Monitor with Relay (TON-0007)
U
s
e
r
M
a
n
u
a
l
U
s
e
r
M
a
n
u
a
l

Specifications

Power supply
Consumption
CO2 sensor
CO
measuring range
2
Accuracy@25℃(77℉),2000ppm
Response time
Warm up time for each turning-on
6 LED lights
On/Off output for control CO2 level
Operation conditions
Storage conditions
Dimensions
Net weight
Installment standard
Housing and protection class
Standard approval
Version

Mounting and Wire Connection

 Notice the supply power voltage of the detector: 24VAC. Do not install the detector on voltages
higher than marked on the detector.
 Firstly, prepare a flat head screwdriver and put it inside of the hole on the top of the detector
housing following step 1, and then open the cover from step 2 to step 4 in next page fig.1.
 Mount the wall plate first, dimensions see next page fig. 2.
Connect wires to terminal strips, (see fig. 3).
Follow step 5 to step7 in fig. 4 to close the cover.
24VAC/VDC
1.5 W Max ; 0.8 W avg
Infrared Sensor with lifetime of 15 years
ABC Logic Self Calibration (default: effective)
0~2,000ppm
±40ppm + 3% of reading or ±75ppm (whichever is greater)
<2 minutes for 90% step change
2 hours (first time)
2 min (operation)
1
st
green light on as CO2 measurement≤600ppm
1
and 2
green lights on as CO2 measurement>600ppm and≤800ppm
st
nd
1
yellow light on as CO2 measurement>800ppm and≤1,200ppm
st
1
st
and 2
nd
yellow lights on as CO2 measurement>1,200ppm and≤1,400ppm
1
st
red light on as CO2 measurement>1,400ppm and≤1,600ppm
1
st
and 2
nd
red lights on as CO2 measurement>1,600ppm
<240VAC/30VDC 3A switching current (resistance load),
0~50℃(32~122℉); 0~95%RH, non condensing
0~50℃(32~122℉);
100mm×80mm×28mm (H X W X D)
180g
65mm×65mm (2"×4") wire box
PC/ABS fire proof material with IP30
CE-Approval
TSM-CO2-1A1R-ST02_65 (SE)
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TON-0007 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for CO2 Meter TON-0007

  • Page 1 Tongdy CO2 Monitor with Relay (TON-0007) Specifications Power supply 24VAC/VDC Consumption 1.5 W Max ; 0.8 W avg Infrared Sensor with lifetime of 15 years CO2 sensor ABC Logic Self Calibration (default: effective) measuring range 0~2,000ppm Accuracy@25℃(77℉),2000ppm ±40ppm + 3% of reading or ±75ppm (whichever is greater) Response time <2 minutes for 90% step change...
  • Page 2 Fig.1 open the cover Fig.4 close the cover Fig.2 wall plate 28.00 3.00 55.00 4.50 8.00 45.00 60.00 jump selection Fig.3 wiring diagram 400ppm 1200ppm Connection Function Electrical Data J6J5 1600ppm 800ppm Terminal Common Power (+) 24VAC/VDC + Line Power ground (-) 24VAC/VDC Voltage 24VAC...

Table of Contents