Features; Specifications; Installation And Operating Instructions - Macurco CM-12 User Instructions

Carbon monoxide detector, controller and transducer
Hide thumbs Also See for CM-12:
Table of Contents

Advertisement

Available languages

Available languages

Features

ETL LISTED Certified to CAN/CSA Std. C22.2 No 61010-1 Conforms to UL Std. 61010-1
Low level meter capable of displaying from 0-200 ppm of CO
The CM-12 meets the Uniform Building Code for enclosed garages and meets OSHA standards for CO exposure
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
CM-12 mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & Alarm relay to activate
Calibration kit is available. One screw allows access for calibration or gas test

Specifications

Power: 100-240VAC (50 TO 60 HZ)
Current: 1.0 A MAX
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
Color: Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation: selectable at diS (disable), 15 ppm, 25 ppm, 35 ppm (default), 50 ppm or 100 ppm CO
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. default or N.C.
Alarm relay settings: diS, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default)
Current Loop, 4-20 mA for 0-200 ppm CO
Buzzer: 85 dBA at 10cm settable to off (default) or on
Digital display: 3 digit LED selectable to off (default) or on.
Operating Environment: 0°F to 125° F (-18C to 52C).10 to 90% RH non-condensing
Operating altitude: Up to 5,000m (16,404ft)

INSTALLATION AND OPERATING INSTRUCTIONS

The following instructions are intended to serve as a guideline for the use of the Macurco CM-12 Carbon Monoxide Detector. It is not to
be considered all-inclusive, nor is it intended to replace the policy and procedures for each facility. If you have any doubts about the
applicability of the equipment to your situation, consult an industrial hygienist or call Technical Service at 1-877-367-7891.
selectable to off or on (default)
,
6

Advertisement

Table of Contents
loading

Table of Contents