Page 4
CM-E1 Carbon Monoxide Detector The CM-E1 is a low voltage detector of Carbon Monoxide. The CM–E1 is designed for connection to UL Listed Fire Alarm/Burglary Control Panels. The CM-E1 is intended for non-hazardous locations such as residences, retail stores, office buildings, and institutional buildings ...
Page 5
The usual sources of Carbon monoxide are defective heat sources such as furnaces or wood burning stoves and automobiles running in adjoining garages. The CM-E1 can detect CO from these sources, as well as any other sources of CO Detector alarms at multiple levels...
Page 6
CM-E1 Carbon Monoxide and Hydrocarbon Fuels Carbon monoxide is colorless, odorless gas resulting from the incomplete combustion of hydrocarbon fuels. Carbon monoxide interferes with blood's ability to carry oxygen to the body's tissues and results in numerous adverse health effects ...
Page 7
CM-6 Carbon Monoxide and Hydrocarbon Fuels CO Level in Air Health Effects 0 ppm Fresh Air 100 ppm Slight headache after 1‐2 hours. 200 ppm Dizziness, headache, nausea after 2‐3 hours. 400 ppm Dizziness, headache, nausea after 1‐2 hours / life threatening after 3 hours. 800 ppm Dizziness, headache, nausea after 45 minutes, unconscious after 1 hour, death within 3 hours. 1,600 ppm Dizziness, headache, nausea after 20 minutes, death within 2 hours. 3,200 ppm Dizziness, headache, nausea after 10 minutes, death within 60 minutes. 6,400 ppm Dizziness, headache, nausea after 1‐2 minutes, death within 30 minutes. 12,800 ppm Instantaneous effects, death within 3 minutes.
Page 8
CM-E1 Carbon Monoxide and Hydrocarbon Fuels The CM-E1 continuously monitors the ambient air at the sensor. If the CM-E1 measures levels of CO greater than the danger level, the RED light will turn on, the Alarm Relay will switch to actuate the alarm circuits in the control panel, and the buzzer on CM-E1 will sound.
Page 9
Test Gas. This field test gas allows installers to do a Functional Test of the CO sensor. The flow rate of the CME1-FTG is 10 LPM providing enough gas to quick test 20-30 CM-E1 Carbon Monoxide sensors Quickly press the TEST/RESET button 5 times.
Page 11
GD-2B and Heating Gases: Propane and Methane The GD-2B is a low voltage electronic detector of combustible, heating type gases designed for connection to Fire Alarm/Burglary Control Panels. This product is for use in ordinary indoor locations of family living units and office workspaces. ...
Page 12
GD-2B and Heating Gases: Propane and Methane Gas boilers, furnaces, water heaters, clothes dryers, fireplaces and stoves are usual sources of gas leaks. The GD-2B can detect gas from these sources, as well as any other sources of combustible gas ...
Page 14
GD-2A and Heating Gases: Propane and Methane The GD-2A is a low voltage electronic detector of combustible, heating type gases designed for connection to UL Listed Fire Alarm/Burglary Control Panels. This product is for use in ordinary indoor locations of family living units and office workspaces.
Page 15
GD-2A and Heating Gases: Propane and Methane Gas boilers, furnaces, water heaters, clothes dryers, fireplaces and stoves are usual sources of gas leaks. The GD-2A can detect gas from these sources, as well as any other sources of combustible gas ...
Page 16
Heating Gases: Propane and Methane Propane also known as Liquefied Petroleum (LP) gas is fuel for many homes, businesses, private and municipal vehicle fleets, school buses, taxis, forklifts and other indoor industrial vehicles Propane is stored as a liquid and converted into a gas inside a tank or a cylinder.
Page 17
Heating Gases: Propane and Methane Sources of Methane gas include Landfills; from the decomposition of wastes, livestock and manure management, Natural Gas utilities or Natural Gas powered vehicles and maintenance facilities Methane (CH ) is a colorless, odorless gas with flammability limits in air of 5.3% to 15% ...
Page 19
HD-11 and Hydrogen Gas The HD-11 is a low voltage electronic detector of Hydrogen gas. The HD-11 is designed for connection to Fire Alarm/Burglary Control Panels. The HD-11 is intended for installation in buildings in non- hazardous locations where hydrogen gas may be present ...
Page 20
HD-11 and Hydrogen Sources of Hydrogen include battery charging stations for golf carts, forklifts or automobiles, battery back-up in IT rooms or telecommunication towers and fuel cell or hydrogen powered vehicles and maintenance facilities Lead-Acid batteries generate Hydrogen (H gas during recharging ...
Page 21
120VAC to 12VDC transformer CM-E1 Adaptor Kit 2-Gang to Single-Gang Adaptor Plate Kit; CM-15/15A to CM-E1 Conversion or GD-2A to GD-2B Conversion CME1-PCA Wire Harness Replacement 6-conductor pigtail cable for use with the CM-E1 Carbon Monoxide Detector...
Need help?
Do you have a question about the CM-E1 and is the answer not in the manual?
Questions and answers