Operation
•
Flashes the SUPERVISORY yellow LED.
•
Activates Special Function Zone ZF21 (MN supervisory zone).
•
Does not suppress Fire or any other activations.
•
Does not activate "General Supervisory" type ID.
•
Any device programmed for "Resound by Supervisory" will not resound.
•
Displays ACTIVE:ECS/MN SUPT or ACTIVE:ECS-MN SUPL in the display, as well as other information specific to the
supervisory message.
•
Sends an MN Supervisory message to the history buffer and installed printer and annunciators.
•
Sends an MN supervisory message (ZF21) out to the network.
Network Activation
•
Logic Zones with ZF21 (MN supervisory zone) will be evaluated.
4.1.3 MN Trouble
MN Trouble Activation
MN troubles are block acknowledged.
NOTE:
NFS2-3030, NCA-2 MN Activations
Local Activation
When an MN trouble activates locally, it:
•
Produces a pulsed audible tone if the piezo is enabled.
•
Activates the panel's trouble relay.
•
Flashes the TROUBLE yellow LED.
•
Activates Special Function Zone ZF22 (MN trouble zone).
•
Does not suppress Fire or any other activations.
•
Is acknowledged with a block acknowledgement.
•
Uses the TROUBLE/SCROLL DISPLAY key for scrolling.
•
Increments the trouble counter on the Events Code screen.
•
Activates "General Pending" type code at the NFS2-3030
•
Activates "General Trouble" and "Trouble Pending" type codes at the NFS2-3030.
•
Any device programmed for "Resound by Trouble" will not resound.
•
Displays MN TROUBLE in the upper left corner of the display, as well as other information specific to the supervisory message.
•
Sends an MN trouble message to the history buffer and installed printer and annunciators.
•
Appears as "MNT" in the Multiple Events list screen, grouped under "TROUBLE".
•
Sends an MN trouble message (ZF22) out to the network.
Network Activation
•
NETWORK MN ACTIVE will display if all systems are normal.
•
Logic Zones with ZF22 (MN trouble zone) will be evaluated.
NFS2-640, NFS-320/SYS MN Activation
Local Activation
When an MN trouble activates locally, it:
•
Produces a pulsed audible tone if the piezo is enabled.
•
Activates the panel's trouble relay.
•
Flashes the TROUBLE yellow LED.
•
Activates Special Function Zone ZF22 (MN trouble zone).
•
Does not suppress Fire or any other activations.
•
Does not activate "General Supervisory" type ID.
•
Any device programmed for "Resound by Trouble" will not resound.
•
Activates "General Trouble" or "Trouble Pending" type code.
•
Sends an MN Trouble message to the history buffer and installed printer and annunciators.
•
Sends an MN trouble message (ZF22) out to the network.
Network Activation
•
Logic Zones with ZF22 (MN trouble zone) will be evaluated.
38
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Mass Notification Events