Programming
3.2.2 LOC
An LOC is comprised of a DVC in LOC mode, (with an NCA-2 or NFS2-3030 in network display mode) or a DVC-RPU combined with
an LCD-160. The LCD-160 must be associated with the NCA-2 or NFS2-3030 (in network display mode) that is being used for the
ACU. The DVC-RPU must be associated with the DVC used for the ACU.
1 Set the MN mode, enable paging levels.
2 Enter associated NFS2-3030*/NCA-2 node number.
3 Program input categories and priorities
4 Create and program an MN Active Tone
5 Create and program a Fire Active Tone (when Fire is the highest priority).
1 Enable Paging Levels for which All Call functionality is required.
2 Program the DAL address - critical to LOC operation
1 Program RDP address - critical to LOC operation.
1 Set the MN Control Field to LOC.
* NFS2-3030 must be in network display mode to function as part of an LOC.
3.2.3 CCS
A CCS is comprised of an NFS2-3030 and a DVC, or an NCA-2 and a DVC, or an ONYXWorks Workstation.
1 Set the mass notification priority.
2 Set the DCC field.
3 Set the MN Control Field to CCS.
4 Map to MN nodes.
5 Program with MN type IDs.
6 Program with MN Special Function Zones.
* NFS2-3030 must be in network display mode to function as part of a CCS.
1 Set the MN mode, enable paging levels.
2 Enter associated NFS2-3030/NCA-2 node number.
3 Program input categories and priorities.
4 Create and program an MN Active Tone.
5 Create and program a Fire Active Tone (when Fire is the highest priority).
1 Set the workstation to FCC Mode.
2 Set the DCC field to disabled
3 Configure the Notify-IP feature.
16
LOC Programming Steps
DVC
Field
DVC-RPU
LCD-160
NFS2-3030*/NCA-2
CCS Programming Steps
NFS2-3030*/NCA-2
Field
DVC
ONYXWorks Workstation
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Programming Steps
Refer to:
page 21
page 19
page 21, page 22
page 25
page 29
page 33
page 33
page 33
page 35
Refer to:
page 19
page 18
page 35
page 23, page 23
page 24
page 25
page 21
page 19
page 21, page 22
page 25
page 29
manual
manual
manual