Siemens SIMATIC ET 200S Manual page 12

Distributed i/o 2ai rtd hf analog electronic module
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Properties
1.1 2AI RTD HF analog electronic module (6ES7134-4NB51-0AB0)
Use of Cu10 sensors
● Select "Three-wire thermal resistor" and "Cu10" at parameter assignment.
● Wire the Cu10 sensor in accordance with the three-wire connection method.
● Automatic, internal compensation of line resistance for the missing measuring line occurs
Note
Please note the following to ensure optimum line compensation in the case of Cu10:
• The sum of the cable resistance and measurement resistance must not exceed 31 Ω.
• The cable must have a resistance of no more than 8 Ω if you want to use the
12
during operation.
temperature range up to and above 312 °C.
Example: A 200 m Cu cable with a 0.5 mm
approximately 7 Ω. A smaller cross-section shortens the permissible cable length
accordingly.
conductor cross-section has
2
2AI RTD HF analog electronic module (6ES7134-4NB51-0AB0)
Manual, 05/2007, A5E01076876-02