Siemens SIMATIC ET 200S Manual page 10

Distributed i/o 2ai rtd hf analog electronic module
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Properties
1.1 2AI RTD HF analog electronic module (6ES7134-4NB51-0AB0)
Current consumption
Power dissipation of the module
Diagnostics function
Measuring principle
Integration and cycle time/resolution per channel:
Noise suppression for
f = n x (f1 ± 1%), (f1 = interference frequency)
Crosstalk between the inputs
Operational limit (in the entire temperature range,
with reference to the input range)
10
From load voltage L+
Group error
Diagnostic functions readable
Integration time can be assigned parameters
Interference frequency suppression in Hz
Integration time in ms
Basic conversion time incl. integration time in
ms
Additional conversion time for wire break
check diagnosis in ms
Additional conversion time in ms for line
compensation in three-wire connections
Cycle time in ms
Resolution (including overshoot range)
Common-mode interference (U
Series-mode interference
(peak interference value < rated value of input
range)
Resistance-type sensor
Pt100, Pt200, Pt500, Pt1000 Standard
Pt100, Pt200, Pt500, Pt1000 Climatic
Ni100, Ni120, Ni200, Ni500, Ni 1000 Standard
and Climatic
Cu10
Max. 30 mA
Typically 0.6 W
Status, interrupts, diagnostics
Red LED "SF"
Yes
Analog value generation
Integrating (sigma-delta)
Yes
60
16,7
50
5
50
Number of active channels per module x
conversion time
Pt 100; Ni 100; Ni120; Pt 200; Ni 200; Pt 500; Ni
500; Pt 1000; Ni 1000; Cu 10 / 15 bits + sign
150 Ω; 300 Ω; 600 Ω; 3000 Ω; / 15 bits
PTC
Suppression of interference, limits of error
)
Min. 90 dB
SS
min. 70 dB
Min. -50 dB
± 0,1 %
± 1.0 K
± 0.25 K
± 0.4 K
± 1.5 K
2AI RTD HF analog electronic module (6ES7134-4NB51-0AB0)
50
20
60
5
60
/ 1 bit
1
Manual, 05/2007, A5E01076876-02