Commissioning; Outlet Grille And Fixing The Covers; Move The Supply Connections - Alpha-InnoTec GKA 6 Operating Manual

Fan coils for heating and cooling
Table of Contents

Advertisement

Commissioning

Check the following before switching on the fan coil:
The unit must be connected to the building's earth-
ing system and appropriate electrical protection el-
ements must be installed (automatic circuit break-
er)...
The condensate drain line must be in working order
(for cooling at flow temperatures below 18°C)...
The air filter must be correctly installed...
The air outlet side must not be blocked or impaired
in any way.
NOTE.
Vent the lines before starting up the system!
All heat exchangers are equipped with a vent valve. The
vent plug is located on the left above the return connec-
tion of the heat exchanger.
16

OUTLET GRILLE AND FIXING THE COVERS

The grilles are latched into place on the unit. They only
have to be lifted up to remove them.
The fan coils are delivered with forward-facing venti-
lation slots made in the factory.. If the grille is rotated
through 180°, the air outlet switches from the front to
the rear.
For units in public places such as schools, libraries, shop-
ping centres, etc, it is possible to block access to the
switch box and the water connections with the help of
a screw.
1 Remove cover and screw
cover into this hole

MOVE THE SUPPLY CONNECTIONS

The structural circumstances on site may require the
supply connection side to be moved. In this case, pro-
ceed as follows:
Dismount the 2 point valve on the heat exchanger
Remove the temperature sensor in the heat ex-
changer and later guide it to its original position
from the opposite side.
Undo the retaining screws of the control box and
screw them into the openings provided on the op-
posite side. It is not necessary to open or discon-
nect the control box...
Undo the retaining screws of the terminal box and
use self-tapping screws to fix it to the other side.,
Dismantle the access panels of the heat exchang-
ers...
We reserve the right to modify technical specifications without prior notice.

Advertisement

Table of Contents
loading

Table of Contents