15. Electronic Function

15.1 Abbreviation

T1: Indoor room temperature
T2: Coil temperature of indoor heat exchanger
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Td: Target temperature

15.2 Display function

15.2.1 Icon explanation on indoor display board
(Duct)
PRE-DEF indicator(cooling and heating type)
or fan only indicator(cooling only type)
Timer indicator
Operation lamp
Temporary button
OPERATION TIMER DEF./FAN ALARM
MANUAL
15.2.2 Icon explanation on indoor display board
(Compact cassette).
15.2.3 Icon explanation on indoor display board
(slim Cassette).
15.2.4 Icon explanation on indoor display board
(Ceiling Floor)

15.3 Main Protection

15.3.1 Three minutes delay at restart for
compressor
1 minute delay for the 1
minutes delay for others.
15.3.2
compressor top
The unit will stop working when the compressor
Alarm indicator
Infrared signal receiver
top temp. protector cut off, and will restart after
Display digital tube
the compressor top temp. protector restart.
15.3.3
compressor discharge
When the compressor discharge temp. is
getting higher, the running frequency will be
limited as below rules:
---Compressor discharge temp. T5>115 ℃
(239°F) for 5s, compressor stops and restarts
up till T5<90℃(194°F)
---110<T5<115℃(239°F), decrease the
frequency to the lower level every 2 minutes.
---105(221°F)<T5<110℃(230°F), keep running
at the current frequency.
----T5<105℃(221°F), no limit for frequency.
15.3.4 Fan speed malfunction
When indoor fan speed keeps too low (lower
than 300RPM) for 50s, the indoor fan will shut
off and restart 30s later, if protection happened
3 times when fan motor restarts continuously,
the unit will stop and the LED will display the
failure.
When outdoor fan speed keeps too low (lower
than 100RPM) or too high (higher than
1500RPM) for 60s, the unit will stop and the
LED will display the failure. Malfunction is
cleared 30s later.