Kohler GM87448 Operation page 18

Industrial generator set
Table of Contents

Advertisement

Parameter Name
Battery Type
AGM 12 V
AGM 24 V
Gel 12 V
Gel 24 V
NiCad 12 V
NiCad 24 V
Output Enable
Forced Charge Cycle
Reset
Charger Voltage
Default 12 V
Bulk (V)
Default 24 V
FLA 12 V
FLA 24 V
AGM 12 V
AGM 24 V
Gel 12 V
Gel 24 V
NiCad 12 V
NiCad 24 V
Charger Voltage
Default 12 V
Absorption (V)
Default 24 V
FLA 12 V
FLA 24 V
AGM 12 V
AGM 24 V
Gel 12 V
Gel 24 V
NiCad 12 V
NiCad 24 V
Charger Voltage
Default 12 V
Float (V)
Default 24 V
FLA 12 V
FLA 24 V
AGM 12 V
AGM 24 V
Gel 12 V
Gel 24 V
NiCad 12 V
NiCad 24 V
Charger Voltage
Default 12 V
Equalize (V)
Default 24 V
FLA 12 V
FLA 24 V
AGM 12 V
AGM 24 V
Gel 12 V
Gel 24 V
NiCad 12 V
NiCad 24 V
18
Range
Default Settings
-40 – 0
-30
-80 – 0
-60
-40 – 0
-30
-80 – 0
-60
-40 – 0
0
-80 – 0
0
Active
Active
Inactive
Inactive
Active
Inactive
13 – 15
14.25
26 – 30
28.5
13 – 15
14.25
26 – 30
28.5
13 – 15
14.25
26 – 30
28.5
13 – 15
14.25
26 – 30
28.5
13 – 16
14.5
26 – 32
29
13 – 15
14.25
26 – 30
28.5
13 – 15
14.25
26 – 30
28.5
13 – 15
14.25
26 – 30
28.5
13 – 15
14.25
26 – 30
28.5
13 – 16
14.5
26 – 32
29
13 – 14
13.25
26 – 28
26.5
13 – 14
13.25
26 – 28
26.5
13 – 14
13.8
26 – 28
27.6
13 – 14
13.6
26 – 28
27.2
12 – 16
14.5
24 – 32
29
Not available
Not available
Not available
Not available
14 – 16
15.5
28 – 32
31
Not available
Not available
Not available
Not available
Not available
Not available
Not available
Not available
Not available
Not available
Not available
Not available
Description
Output Enable is always on and controlled
by the generator controller.
This feature allows a user to manually trigger
a refresh cycle where the charger goes into
the bulk cycle and cycles through the
charger cycle.
These is a single trigger of the feature. The
value returns to inactive automatically once
the action is triggered.
Target bulk voltage setpoint
Target absorption voltage setpoint
Target float voltage setpoint
Target equalize voltage setpoint.
Note: The controller's high battery voltage
warning voltage shall set 0.2 V higher
then this value to avoid nuisance high
battery warnings while charger
performs the equalize cycle.
TP-7077