8 Technical Data

8.1 Electrical specifications

NOTE: About these ratings - The DURACELL HUB is a peripheral component of the DURACELL POWER CENTER 5KW. It is a power
distribution center with an on-board energy management system. As such, this product is defined under the category of
Interconnection System Equipment (ISE) for use in utility interactive and/or stand-alone power systems under the scope of the
UL1741 Standard, and is intended to be operated in parallel with an electric power system (EPS) to supply power to common loads.
The DURACELL HUB as a standalone device does not provide grid-interactive functionality. Where necessary, the ratings included
below are listed both as a standalone product, as well as in conjunction with the Standard for Interconnecting Distributed Resources
With Electric Power Systems, IEEE 1547, and the Standard for Conformance Test Procedures for Equipment Interconnecting
Distributed Resources with Electric Power Systems, IEEE 1547.1.
AC ratings – Power distrubution circuits
Nominal Grid voltage
Nominal Grid frequency
Maximum continuous operating current (or Rated
current), AC
Maximum continuous operating power (or Rated
power), VA
Maximum AC fault current and duration (short
circuit)
AC connections, number - type
AC voltage operating range
AC frequency operating range
Maximum output overcurrent rating, grid & backup
connection
Protective Class (I, II, or III)
Over-Voltage Category (OVC I, II, III, or IV)
Pollution Degree
Lightning protection
General data
Width x height x depth
Weight
Protection type
Ambient temperature, relative humidity, altitude
Cooling method
Installation type
Enclosure material
For use only with the DURACELL POWER CENTER 5KW

8.2 Wire and torque ratings

Use solid copper only, 90 °C or higher rating
PCS (AC)
# conductors
AC grid, load
3 conductor + PE
AC PCS grid, PCS load
3 conductor + PE
Ground Lug
1 conductor
Optional breakers
2 pole
240V/120V split phase
60 Hz
40.0 Amps
9600 VA
14.0 Apk, 2.5 Arms (duration 63.5 ms)
4 – Grid, Load, PCS Grid, PCS Load
Max: 100 to 264 Vac. Note: UL 1741SA compliant operating limits are
determined by the D-5kW PCS configuration settings
Max: 47 to 63 Hz. Note: UL1741SA compliant operating limits are
determined by the D-5kW PCS configuration settings
40.0 Amps
Class I
OVC III
3
IEEE 62.41.2, location category B, low exposure
15.3" x 17.3" x 6.7" (389 x 440 x 170 mm)
23 lbs (10.5 kg)
Type 3R
-20 °C to +50 °C, 95%, 2000 m
Natural convection
Wall-mount (upright)
Halogen free, self extinguishing fiberglass reinforced polyester
AWG (min to max)
10 AWG to 6 AWG
10 AWG to 6 AWG
10 AWG to 6 AWG
10 AWG to 6 AWG
Torque
Push-lock, spring cage
Push-lock, spring cage
15.9 in-lbs
17.7 in-lbs
14