Installation Instructions; Electrical Wiring Instructions; Emc Cable Connection; Ak1 Cable Connection - Duracell D-HUB Installation Manual

Table of Contents

Advertisement

3 Installation Instructions

1.
Mount the DURACELL HUB on the
wall using the 4 mounting screw
holes on the top and bottom
flanges. (Mounting hardware not
included).
2.
Using the conduit plan in section
2.2, drill the knockout holes
required for the conduit runs on the
bottom face of the enclosure.
Constrain the drill area as shown.
3.
Route all conduit as cabling as
required.
CAUTION! All knockout holes must be sealed to maintain the Type 3R environmental rating of the enclosure after
the installation is complete.
CAUTION! The restricted knockout area is near the DURACELL HUB circuitry, so extra care must be taken to avoid
internal components when the knockout holes are being drilled.
CAUTION! Ensure that the DURACELL HUB enclosure door is properly seated such that the gasket becomes
compressed when the door is securely closed.

4 Electrical Wiring Instructions

IMPORTANT! Wiring methods must be in accordance with local electrical codes. The installer is responsible for
ensuring that over-current protection is installed and sized appropriately for the AC circuits, in accordance with the
National Electrical Code, ANSI/NFPA 70, Canadian Electrical Code and local codes
The patch cables provided in section 4.1 and 4.2 below have pre-assembled connectors at both ends. It is strongly
recommended that these cables are pulled in conduit prior to the power cables.
CAUTION! Do not install cables if any wires appear damaged
or are not terminated improperly. Contact your distributor
for support.

4.1 EMC Cable Connection

1.
Terminate the EMC CAT 5 patch cable in the RJ-45
port as shown.
NOTE: If a longer extension is required, shielded CAT 5/6 cable
must be used.

4.2 AK1 Cable Connection

1.
Plug in the AK1 DURACELL HUB control cable
connector into the terminal block.
NOTE: If an AC source disconnect was installed between the
DURACELL HUB's grid port and the ESS as described in section
2.4 of this manual, leave the AK1 terminal block unplugged
until the system has permission to operate.

4.3 AC Power Connections

All AC power connections to L1, L2, and Neutral are terminated
with a hinged pressure clamp connector. Observe the connector
termination instructions for the clamp connector as shown in
figure 15. Recommended strip length is 18 mm (11/16").
Restricted knockout area:
1.0
7" W x 4" H
Figure 12: Recommended knock-out area.
Figure 13: EMC cable connection to RJ-45 port.
Figure 14: AK1 cable connection.
1.0"
Knockout area:
5" W x 4" H
1.0"
1.0"
8