M-system R7L-SV4-R Instruction Manual page 12

Dc voltage/current input module, 4 points
Table of Contents

Advertisement

■ FUNCTIONAL BLOCK: fbARM[0...3]
nv 72
...nv 75
• Network Variables
TYPE
NETWORK
{ Range }
VARIABLE
{ Default }
{SNVT_lev_percent}
{-163.840...163.835}
{0.0}
{SNVT_temp}
{-274.0...6279.5}
{0.0}
nviARMIn
{SNVT_temp_p}
{-273.17...327.66}
{0.0}
{SNVT_count_32}
{0...999 999 999}
{0}
{SNVT_switch}
nvoARM1
{0.0 0}, {100.0 1}
{0.0 -1}
{SNVT_switch}
nvoARM2
{0.0 0}, {100.0 1}
{0.0 -1}
{SNVT_switch}
nvoARM3
{0.0 0}, {100.0 1}
{0.0 -1}
{SNVT_switch}
nvoARM4
{0.0 0}, {100.0 1}
{0.0 -1}
SEN TRONIC
fbARM [0...3] (Object ID : 33...36)
Network Variables
nviARMIn
SNVT_lev_percent
SNVT_temp
SNVT_temp_p
SNVT_count_32
Configuration Properties
nviARMIn :
SCPTnumDigits
Set the value source
SCPTnvType
Network variable type
SCPTsetpoint [ ]
Alarm setpoint
SCPToffset
Alarm deadband
EXPLANATIONS
Inputs the value to be compared to the alarm setpoint.
nviARMIn alarm 1 (HH)
{100.0 1} with nviARMIn ≥ SCPTsetpoint[0]
Reset to {0.0 0} from {100.0 1} with nviARMIn < (SCPTsetpoint[0] – SCP-
Toffset)
nviARMIn alarm 2 (H)
{100.0 1} with nviARMIn ≥ SCPTsetpoint[1]
Reset to {0.0 0} from {100.0 1} with nviARMIn < (SCPTsetpoint[1] – SCP-
Toffset)
nviARMIn alarm 3 (L)
{100.0 1} with nviARMIn ≤ SCPTsetpoint[2]
Reset to {0.0 0} from {100.0 1} with nviARMIn > (SCPTsetpoint[2] + SCP-
Toffset)
nviARMIn alarm 4 (LL)
{100.0 1} with nviARMIn ≤ SCPTsetpoint[3]
Reset to {0.0 0} from {100.0 1} with nviARMIn > (SCPTsetpoint[3] + SCP-
Toffset)
056 222 38 18
AG
nvoARM1
nv 76
SNVT_switch
...nv 79
nv 80
nvoARM2
SNVT_switch
...nv 83
nvoARM3
nv 84
SNVT_switch
...nv 87
nvoARM4
nv 88
SNVT_switch
...nv 91
mailbox@sentronic.com
www.sentronic.com
R7L-SV4
EM-7804-A Rev.5 P. 12 / 18