Haier GE NF96UV Service Manual page 39

96% upflow/horizontal two stage variable speed gas furnace
Hide thumbs Also See for GE NF96UV:
Table of Contents

Advertisement

Elbow
Tubing
Figure 41. Field-Provided Drain Components
CAUTION
Do not use copper tubing or existing copper condensate
lines for drain line.
1.
If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in the
Start-Up section.
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
Drain Pan
31-5000726 Rev. 0
Barbed Fitting
Hose Clamp
(Unit shown in horizontal left-hand discharge position)
Evaporator
Coil
Condensate
Drain Connection
(Trap at coil is optional)
Piping from furnace and evaporator coil must slope down a minimum 1/4" per ft. toward trap
Figure 39. Furnace with Evaporator Coil Using a Separate Drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heating cable kit is
available in various lengths; 6 ft. (1.8m) - kit no. 26K68;
24 ft. (7.3m) - kit no. 26K69; and 50 ft. (15.2m) - kit no.
26K70.
(Trap at coil is optional)
Field Provided Vent
(1" min. 2" max. above
condensate connection)
Condensate
Drain Connection
Figure 40. Furnace with Evaporator Coil Using a
4"min
5"max
5' max.
PVC Pipe Only
Page 39
Evaporator drain
line required
Separate Drain
Field Provided Vent
(4" min. to 5" max. above
condensate drain connection)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents