Siemens SIMATIC ET 200S M151-3 PN Manual page 36

Distributed i/o interface module
Table of Contents

Advertisement

Functions
3.4 PROFIenergy
Parameter data record
The parameter data record is provided by FB 53.
Table 3- 6
Parameter data record for PROFIenergy, Index 3
Byte
Element
0
Version
1
Number of blocks
2
Block 1
Slot number
3
Mode
4
Block 2
Slot number
5
Mode
6
Block 3
Slot number
7
Mode
:
:
:
16
Block 8
Slot number
17
Mode
PROFIenergy data records
The data record for PROFIenergy, Index 80A0, supports the following services:
Service
Start Pause
End Pause
Query Modes
PEM status
PE_Identify
36
Coding
01
03
00
00
00
00
00
00
:
00
00
Service ID
Meaning
0x01
Disconnects load voltage and suppresses the corresponding diagnoses
0x02
Connects the load voltage, post-configures the modules in the potential group
0x03
Reads the supported modes
Request List Energy Saving Modes
Request Get Mode (Energy Saving Mode Data)
0x04
Reads the PROFIenergy status
0x05
Reads the supported PROFIenergy services
Explanation
Cannot be modified
Value range 1 ... max. example: There are eight parameter
blocks to follow.
00:
Not available
1 ... 62:
Slot of the power module to be switched off
Bit 0:
0: Continue Work
1: Switch off
Bit 1 ... 7:
Reserved
00:
Not available
1 ... 62:
Slot of the power module to be switched off
Bit 0:
0: Continue Work
1: Switch off
Bit 1 ... 7:
Reserved
00:
Not available
1 ... 62:
Slot of the power module to be switched off
Bit 0:
0: Continue Work
1: Switch off
Bit 1 ... 7:
Reserved
:
:
00
Not available
1 ... 62
Slot of the power module to be switched off
Bit 0:
0: Continue Work
1: Switch off
Bit 1 ... 7
Reserved
Interface module IM151-3 PN HIGH FEATURE (6ES7151-3BA23-0AB0)
Manual, 08/2010, A5E01584258-04

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7151-3ba23-0ab

Table of Contents