Siemens SIMATIC ET 200S M151-3 PN Manual page 12

Distributed i/o interface module
Table of Contents

Advertisement

Properties
1.1 IM 151-3 PN HIGH FEATURE interface module
Limitations for operation of the modules with IM151-3 PN HIGH FEATURE
The following modules cannot be used with the IM151-3 PN HIGH FEATURE:
2AO U; HIGH FEATURE
2AO I; HIGH FEATURE
1SI serial interface module
Modbus/USS serial interface module
2PULSE
1Count 24V/100kHz
Motor starter
Pin assignment
The following table shows the pin assignment of the IM151-3 PN HIGH FEATURE interface
module for the 24 VDC voltage supply and of the RJ45 interfaces for PROFINET IO:
Table 1- 1
12
Module
Direct starter
Reversing starter
Pin assignment of the IM151-3 PN HIGH FEATURE
View
Up to order number
6ES7135-4LB01-0AB0
6ES7135-4MB01-0AB0
6ES7138-4DF00-0AB0
6ES7138-4DF01-0AB0
6ES7138-4DD00-0AB0
6ES7138-4DA03-0AB0
3RK1301-xxxxx-0AA1
3RK1301-xxxxx-1AA1
Signal name
1 TD
Transmit data +
2 TD_N
Transmit Data –
3 RD
Receive data +
4 GND
Ground
5 GND
Ground
6 RD_N
Receive Data –
7 GND
Ground
8 GND
Ground
1L+
24 VDC
2L+
24 VDC (for loop through)
1M
Ground
2M
Chassis ground (for loop through)
Interface module IM151-3 PN HIGH FEATURE (6ES7151-3BA23-0AB0)
Up to product version
3
3
4
4
6
-
-
-
Name
Manual, 08/2010, A5E01584258-04