Functions
3.3 Option handling
Data record of the example
The following control data record structure applies for the example given above:
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
30
Element
Coding
Block length
17
Block ID
196
Version
1
Version
0
Slot 1
1
Slot 2
2
Slot 3
3
Slot 4
4
Slot 5
0
Slot 6
0
Slot 7
5
Slot 8
6
Slot 9
0
Slot 10
0
Slot 11
7
Slot 12
8
Slot 13
9
Explanation
Header
The configured slot 1 is real slot 1.
The configured slot 2 is real slot 2.
The configured slot 3 is real slot 3.
The configured slot 4 is real slot 4.
The configured slot 5 does not exist.
The configured slot 6 does not exist.
The configured slot 7 is real slot 5.
The configured slot 8 is real slot 6.
The configured slot 5 does not exist.
The configured slot 6 does not exist.
The configured slot 11 is real slot 7.
The configured slot 12 is real slot 8.
The configured slot 13 is real slot 9.
Interface module IM151-3 PN HIGH FEATURE (6ES7151-3BA23-0AB0)