Atom B Series VRF 50/60Hz
6.2 Defrosting Operation 
In  order  to  recover  heating  capacity,  the  defrosting  operation  is  conducted  when  the  outdoor  unit  heat  exchanger  is 
performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor 
heat exchanger temperature, indoor heat exchanger temperature and outdoor unit running time. When the outdoor unit is 
running in defrosting, the digital display on outdoor main PCB will display "df". 
Table 3‐6.5: Outdoor unit component control during defrosting operation
Component 
Inverter compressor   
DC fan motor   
Electronic expansion valve   
Four-way valve 
 
Table 3‐6.6: Indoor unit component control during defrosting operation 
Component 
Electronic expansion valve 
Note: Prevent cold wind: It's only valid in heating operation, and this control is priority to other controls (including heating oil return and defrost), 
Which determine the conversion between setting fan speed with low fan speed and turn off the fan according to the evaporator coil temperature 
T2. 
22 
   
Wiring diagram 
label 
COMP 
FAN 
EEV1 
ST1 
Unit state
Thermo on
Fan 
Standby 
Thermo off
Thermo on
Standby 
Thermo off
 
 
28‐60 model
Control functions and states 
 
Fixed frequency 
Fan speed controlled according to outdoor ambient 
 
temperature (T4) before
Position 480 (steps) 
Off 
Control functions and states 
Operate on setting fan speed (Prevent cold wind priority) 
Operate on setting fan speed (Prevent cold wind priority) 
Off 
480 (steps) 
480 (steps) 
480 (steps) 
 
 
running in defrosting 
 
 